In the New Module window, fill in the following items below. Click OK when done.
• Name. We suggest using a descriptive name like "EliteProV3"
• Com Format: Data-INT (i.e. 16 bits)
• IP Address: Enter the IP address of the option module. In this
example, we used 192.168.0.181.
• Input Assembly: Instance=101, Size=14
• Output Assembly: Instance=102, Size=8
• Configuration Assembly: Instance=128, Size=0
3. Click the Connection Tab and set the Requested Packet Interval (RPI) to the
desired value. Additional options can also be set here. Please refer to Rockwell
Software for additional information. When finished click OK. The newly created
module should be listed under the Ethernet item in the I/O Configuration.
4. When the new module is created, the Logix5000 software automatically creates
Controller Tags for the I/O Assemblies. There will be a parameter group for each
of the assemblies (Input, Output, & Configuration). Note that the Configuration
assembly is not used. Refer to Figure 6 and Figure 7 below. In these examples,
the Description column has been edited to reflect the mappings from Section 4.
5. When the PLC is programmed, it should begin reading the Inputs and writing the
Outputs. Remember to set the Write Control Status register to 1 in order to
enable writing of the outputs to the drive. Refer to Table 6.
14

Figure 5: Logix 5000: Define Module Properties