Calibration (K-Factor)

13.

Setting the K-Factor

13.1
K-Factor is a proportional calibration factor of litres dispensed per revolution of the meter.
To calibrate the dispenser/pump, dispense fuel into a certified measuring container, and
compare the display value with the amount dispensed.
Example:
Display shows 10.00
True volume
To calculate the correct 'K' Factor from the information above; firstly record the existing
'K' Factor.
New
'
K'
Change the existing 'K' Factor to this new value.

Sealing the K-Factor switch

13.2
After calibration the K-factor switch should be sealed as shown