C. WIRING
A MEANS FOR DISCONNECTION MUST BE INCORPORATED IN THE FIXED WIRING IN ACCORDANCE WITH
THE WIRING REGULATIONS.
WARNING: THE POSITIVE VENTILATIION UNIT AND ANCILLARY
CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER
SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.
The Air+ PIV is designed for operation from a single-phase alternating current source
(220-240V AC).
Mains supply voltages (220-240V ac) are present in this equipment which may cause
death or serious injury by electric shock. Only a qualified electrician or installer
should connect the power supply to this unit.
A 2m integral mains flying lead is connected to the unit for connection to a spur.
should be capable of disconnecting all poles, having a contact separation of at least
3mm.
WARNING: If the supply cord is damaged, it must be replaced
by the manufacturer, its service agent or a similarly
qualified person in order to avoid a hazard
Ensure the local AC power supply is isolated.
The product has a pre-wired flying lead.
blue core to Neutral.
Use cable clamps and clips to secure the cable, as appropriate. 
 
Fig.8
IMPORTANT:
In order to have the product
switch off in the event of a fire
it must be wired using a smoke
alarm with a relay system.
Use Fig.9 as a reference and
refer to the instructions
provided by the manufacturer of
the smoke alarm and relay in
order to wire the unit correctly.
Ensure the relay works correctly
by testing the fire alarm; the
unit should switch off when the
alarm is sounding.
Connect the brown core to Live and the
Fig. 9.
8