Descaling
• Use a nitric acid (HNO3) or citric acid
solution: 1.5% concentration by weight, max.
temperature 65°C (1.5% by weight corresponds
to 1.75 l of 62% HNO3 for 100 litres of water) or
a polyphosphate solution (NaPO4 or Na3PO4):
1.5% max. concentration by weight, max.
temperature 50°C.
Degreasing
• Degrease stainless steel or titanium plates
with a sodium hydroxide (NaOH) solution: 1.5%
max. concentration by weight, max. temperature
65°C (1.5% by weight corresponds to 3.75 l of
30% NaOH for 100 litres of water).
• Do not use hydrochloric acid or water with
a chloride content of over 300 ppm to clean
stainless steel plates.
• Do not use phosphoric acid to clean titanium
plates.
Deposits:
Calcium
Recommended detergents: 4% nitric acid
solution at 60°C max. - 4% citric acid solution at
60°C max.
Oils and greases
Recommended detergents: paraffin or kerosene
(as these fluids may damage NBR and EPDM
gaskets, limit the contact time to no more than
30 minutes)
Sludges, metal oxides
Recommended detergents: 8% nitric acid
solution at 60°C max. - 4% citric acid solution at
60°C max.
Organic matter
Recommended detergents: 2% sodium hydroxide
solution at 40°C max.
5.6 - Liquid penetrant testing
• Corrosion, galvanic coupling and erosion
can create holes in the plates. As such damage
is not always visible to the naked eye, we
recommend performing liquid Atlantic tests
to check for holes or microcracks. Atlantic
technical support team can advise you on the
appropriate products.
ATLANTIC BOILERS, PO BOX 11, ASHTON UNDER LYNE, OL6 7TR T: 0161 621 5960 E: [email protected] www.atlanticboilers.com
5.7 - Gasket replacement
• Before starting, check the manufacturing date
of the gaskets, printed on the relevant date stamp
5.7 - Gasket replacement
(Fig.5). Please note that the gaskets must not be
• Before starting, check the manufacturing date o
stored for more than 6-12 months (see chapter 2 -
kets, printed on the relevant date stamp (Fig.5). P
STORAGE).
that the gaskets must not be stored for more
months (see chapter 2 - STORAGE).
• Remove the old gasket without using cut-
• Remove the old gasket without using cutting tools,
ting tools, which could irreparably dam-
which could irreparably damage the plate.
age the plate.
• Make sure that the plate and gasket are
thoroughly clean and dry alongside the
• Make sure that the plate and gasket are
gasket slot.
thoroughly clean and dry alongside the gasket slot.
5.7.1 - Plug-In® Design gaskets
• Press the gasket onto the plate (Fig. 6), making
5.7.1 - Plug-In® Design gaskets
the leak detector vents, "A", are facing up and
the Plug-In® tabs are hooked into their respecti
• Press the gasket onto the plate (Fig. 6), making
(Fig.7). Make sure that the gasket is properly se
sure that the leak detector vents, "A", are facing up
notch, then turn the plate over to check again t
and check that the Plug-In® tabs are hooked into
Plug-In® tabs are correctly in place.
their respective notches (Fig.7). Make sure that the
5.7.2 - Plug-In® Design gaskets which may requi
gasket is properly seated in its notch, then turn the
plate over to check again that all the Plug-In® tabs
• Plug-In® Design gaskets, for initial plates, interme
ing plates (for multi-pass heat exchangers only
are correctly in place.
plates, may require a limited use of glue. Thes
plates, complete with gaskets mounted at the fa
5.7.2 - Plug-In® Design gaskets
be supplied as spare parts. Alternatively, for the
tion of the gaskets, proceed as described below.
may require the use of glue
• Plug-In® Design gaskets, for initial plates,
42
intermediate turning plates (for multi-pass heat
exchangers only) and final plates, may require
a limited use of glue. These types of plates,
complete with gaskets mounted at the factory, can
be supplied as spare parts. Alternatively, for the
substruction
of the gaskets, proceed as described below.
A: Leak detector vents are notches in the surfaces of
the gasket sections around the portholes which vent
any leaks to the atmosphere so that they can be
detected.
of glue
which