CONTROL WIRING
General
All wiring should conform to the National Electric Code and local
regulations.
The total electrical load must not exceed the maximum
rating of the control (see Specifications).
Use copper conductors only.
Electrical leads should not be taut; allow slack for
temperature change and vibration.
Input and Output Wiring
For typical wiring diagrams, refer to Figures 4, 5 and 6. All connections are
made to the power (lower) circuit board. When using the 24 VAC powered
models, the 24 VAC input lines must enter through the sidewall of the case.
Refer to figure 3 for location of the entry hole.
Figure 7 for wiring.
Analog Output
ETC models are available with an optional 0 to 10 volt analog output. This
signal is a linear representation of the sensor temperature with 0 volts = -30°F
and 10 volts = 220°F. See figure 8 for wiring information and figure 3 for
location of the entry hole. The reference for this output is designated by the
"-" symbol on the wiring diagram. The output signal is designated by the "+"
symbol.
120 VOLT
LOAD
Figure 4:
Typical Line Voltage Wiring Diagram.
240 VOLT
LOAD
Figure 5:
Typical Wiring Diagram for 240 VAC Power Input and
Line Voltage Switching.
Figure 6:
Different Voltage to Control and Different Voltage Load.
4
240 VAC
240 VAC
OR
120 VAC
240 VAC
OR
120 VAC