To open the service panel, use the key included with the equipment. The service panel has four closing
points that should be opened to take off the panel:
Both models include a visual dirty filter alarm. When
the led is turned ON, the H14 HEPA filter must be
changed (the lifetime of HEPA filter is around 3.000
hours depending on the environment).
It is recommended to change the other two filters
after:
G4 → 500 working hours
-
F7 → 1.500 working hours
-
Once they are opened, take off the panel using the handle.
Filter reemplacements