HORIZONTAL
The horizontal models have four roof fixing points.
Keep in mind to asure a minimum distance to open
the service panel and to replace the filters. Depending
on the model, this distance is 500mm (Kleenbox
46/46 and Kleenbox 46/76) or 800mm (Kleenbox
76/76).
Assembly, connection and disconnection, electrical wiring and maintenance must be
carried out exclusively by qualified personnel, observing these instructions and in
accordance with the applicable standards. In case a special control is supplied, a
specific manual is attached that must be used for its operation and installation.
It is not necessary to remove the service panel to connect the equipment All the
connections (power and control) and necessary fixings are external (on the lateral of the
equipment). The equipment has a service panel to carry out repairs and replacements
(see "REPAIRS" section).
HORIZONTAL
To connect the power supply on the horizontal
model, the user should find a black connection box
(placed on the lateral). Just connect single phase
230V to supply the fan.
HORIZONTAL
There is a white connection box placed on the lateral,
next to the black power supply box. It is not needed
to open the service panel to connect the control.
It is necessary to connect the fan 0-10V regulation
and the dirty filter visual alarm (see wiring diagram
section).
Control
connection
230Vx1
Power Supply
INSTALLATION
Maintain 300 mm free of obstructions in the inlet
zone.
Power supply
The vertical models include a plug&play wire which
should be connected to the equipment and to a
Shucko wall connector with electrical current.
Control
For the vertical model, the control is inbuilt in the
equipment and do not need any kind of installation.
3
VERTICAL
VERTICAL
VERTICAL