Daikin BRC7EA631 설치 매뉴얼 - 페이지 12

{카테고리_이름} Daikin BRC7EA631에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Daikin BRC7EA631 16 페이지. Wireless remote controller kit
Daikin BRC7EA631에 대해서도 마찬가지입니다: 운영 매뉴얼 (20 페이지)

Daikin BRC7EA631 설치 매뉴얼
(Example)
If the time to clean air filter is set to "Filter Contamination-Heavy", set MODE number to "10", FIRST CODE
number to "0", and SECOND CODE number to "02".
FIRST
MODE
CODE
number
number
0
10
3
1
12 (VRV
system)
2
13
0
NOTE
• The SECOND CODE number is factory set to "01".
Do not use any settings not listed in the table or in the installation manual provided with the indoor unit.
For group control with a wireless remote controller, initial settings for all the indoor units of the group are
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)
11
DESCRIPTION OF SETTING
Filter Contamination-Heavy/Light
(Setting for spacing time of display
time to clean air filter) (Setting for
when filter contamination is heavy,
and spacing time of display time to
clean air filter is to be halved)
Spacing time of display time to
clean air filter count
(Setting for when the filter sign is
not to be displayed)
ON/OFF input from outside
(Set to enable starting/stopping
from remote.)
Thermostat differential changeover
(Set when using remote controller
thermostat sensor.)
Air flow rate increase mode (to be
set upon user's request)
SECOND CODE number
01
Approx.
Light
Heavy
200 hrs.
Display
Forced OFF input
1°C
Standard
NOTE)
02
03
Approx.
100 hrs.
Do not display
ON/OFF
0.5°C
A little increase
Increase
English