Daikin DPS 설치 및 유지 관리 매뉴얼 - 페이지 16
{카테고리_이름} Daikin DPS에 대한 설치 및 유지 관리 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Daikin DPS 20 페이지. Space sensor
Daikin DPS에 대해서도 마찬가지입니다: 설치 매뉴얼 (6 페이지)
11. Click 'Save changes' button
a. IMPORTANT: Allow the page to refresh
b. Confirm that there is number in parentheses next
to "Review Changes". If so, proceed to step 12; if
not, repeat steps 8-11.
12. Remove 'wwan' interface
13. Remove 'wlan0' interface
14. Click the 'Save Changes' button
a. IMPORTANT: Allow the page to refresh
b. Confirm that there is number in parentheses next
to "Review Changes". If so, proceed to step 15; if
not, repeat steps 8-14.
15. Click the 'Apply Changes' button in the lower right-hand
corner of the screen. The page will automatically refresh
when complete (this can take as much as two minutes).
Figure 17: M2M Gateway Home Page
IM 1229-1 • INTELLIGENT EQUIPMENT
16. Confirm that 'ICMP host' of "wan" interface is still set to
"disable"
a. If so, go to step 17.
b. If not, set to "disable"
c. Click 'Save changes' button
i. IMPORTANT: Allow the page to refresh
ii. Confirm that there is number in parentheses
next to "Review Changes". If so, proceed to
step 17; if not, repeat steps 8-16.
d. Click the 'Apply Changes' button in the lower
right-hand corner of the screen. The page will
automatically refresh when complete (this can take
as much as two minutes).
17. Click the 'System' tab, then click the Reboot button.
18. Reconnect the Ethernet cable between the M2M
Gateway and the MicroTech III controller. Procedure
complete.
NOTE: Be certain that the IT staff has allowed incoming and
outgoing internet traffic on TCP ports 80, 443, 3197,
3199, 5222, 5223 and 8080.
16
s
s
-u
ysTem
eT
p
www.DaikinApplied.com