Daikin WMC 설치 및 유지 관리 매뉴얼 - 페이지 7
{카테고리_이름} Daikin WMC에 대한 설치 및 유지 관리 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Daikin WMC 12 페이지. Microtech ii chiller modbus communication module

Figure 7: Serial Card Slot Connectors
NOTE: This operation relies more on fitting the
communication module into the connector than
seeing the connectors mate.
6. Insert the communication module, pointed up, into the
slot. Keeping it level, roll the module into position as
you guide it into the slot, feeling the connectors line up
(Figure
8, Steps 1 and 2).
7. When you feel the connectors align, press the
communication module into the plug. Verify that the
module is firmly connected
Figure 8: Inserting the Modbus Communication Module
www.DaikinApplied.com
(Figure
8, Step 3).
Step 1
8. Mount the plastic cover on the serial card slot. Slip the
cover over the network connector plug
9. Connect the communication module to the network
(Figure 10
and
Figure
a. Route the network cable through the knockout and
to the communication module.
b. Connect one wire of the network cable to Pin 2 of
the connector plug.
c. Connect the other wire to Pin 3 of the connector
plug. Note that no wire is connected to Pin 1
(GND).
Step 3
7
IM 743-7 • MICROTECH II CHILLER UNIT CONTROLLER
Installation
(Figure
9).
11):
Step 2