Daikin DV1-15-2814-FA 설치 및 운영 매뉴얼 - 페이지 4
{카테고리_이름} Daikin DV1-15-2814-FA에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Daikin DV1-15-2814-FA 8 페이지.
MODEL
DV1-15-2117-AB DV1-15-2121-AC DV1-15-2124-AD DV1-15-2814-FA DV1-15-2817-FB DV1-15-2821-FC DV1-15-2824-FD
Airflow - up to
Up to 1200 cfm
maximum rated flow
(2039 m
21 x 17 in
Duct Size
(53 x 43 cm)
0.11 in. w.g.
Pressure Drop*
@ 600 cfm
(Filters Only)
0.26 in. w.g.
@ 1200 cfm
MERV Rating*
Notes:
1. Installation with units with ECM motors recommended.
2. Two filters should be considered for any airflow rates above maximum rated flow or when duct pressure loss is excessive.
Furnace Size
Furnace Riser
AMP-BSRB-1428
When using a furnace riser use DV1-15-2824-FD on all size furnaces
MERV Rating 15 - Minimum Filtration Efficiency @492 fpm: • E1 85% (0.3 - 1.0 micron) • E2 90% (1.0 - 3.0 micron) • E3 95% (3.0 - 10.0 micron)
*Independent testing performed by LMS Technologies, Inc. Specification values may vary due to individual systems.
Filter Match-up Options
Air Handler Filter Options
Air Handler Size
Bottom/Top Return Plenum Return
B
21x17
C
21x21
D
21x24
Turning
Vanes
Dual filter furnace application, side return (For any
side return on a furnace without a furnace riser,
use one DV1-15-2817-FB on A & B or two
DV1-15-2817-FB on C & D furnace sizes)
4
Up to 1600 cfm
Up to 1800 cfm
/h)
(2718 m
/h)
(3058 m
3
3
21 x 21 in
(53 x 53 cm)
(53 x 61 cm)
0.11 in. w.g.
0.11 in. w.g.
@ 800 cfm
@ 900 cfm
0.31 in. w.g.
0.27 in. w.g.
@ 1600 cfm
@ 1800 cfm
15
15
A
B
AMP-BSRB-1728
AMP-BSRB-2128
Furnace Size Bottom/Top Return Side Return
21x21
A
21x24
B
21x24
C
D
Duct transition
Duct transition for side flow dual filter installation furnace/air handler application
Turning
Vanes
www.daikincomfort.com
Specifications
Up to 1200 cfm
/h)
(2039 m
/h)
3
3
21 x 24 in
28 x 14 in
(71 x 36 cm)
0.10 in. w.g.
@ 600 cfm
0.27 in. w.g.
@ 1200 cfm
15
15
C
D
AMP-BSRB-2428
Furnace Filter Options
28x14
28x17
28x17
28x17
28x21
(2) 28x17
28x24
(2) 28x17
Turning
Vanes
Riser
Single filter furnace application, side return
with furnace riser (When using a furnace riser,
use DV1-15-2824-FD on all furnace sizes)
Up to 1600 cfm
Up to 2000 cfm
(2718 m
/h)
(3398 m
/h)
3
3
28 x 17 in
28 x 21 in
(71 x 43 cm)
(71 x 53 cm)
0.10 in. w.g.
0.10 in. w.g.
@ 800 cfm
@ 1000 cfm
0.26 in. w.g.
0.24 in. w.g.
@ 1600 cfm
@ 2000 cfm
15
15
Furnace Riser
Side Return with Furnace Riser
28x24
28x24
28x24
28x24
Furnace Riser
Up to 2000 cfm
(3398 m
/h)
3
28 x 24 in
(71 x 61 cm)
0.08 in. w.g.
@ 1000 cfm
0.19 in. w.g.
@ 2000 cfm
15
IO-DOPAC