6.2
Symptom: You are feeling too cold
(hot) in your living room
Possible cause
The desired room temperature is
too low (high).
The desired room temperature
cannot be reached.
The weather-dependent curve is
set incorrectly.
6.3
Symptom: The water at the tap is
too cold
Possible cause
You ran out of domestic hot
water because of unusual high
consumption.
The desired DHW tank
temperature is too low.
EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596819-1 – 2019.10
Corrective action
Increase (decrease) the desired
room temperature. See
"3.3.2 Room thermostat control -
Using the room temperature
pages" [ 4 6].
home
If the problem recurs daily, do
one of the following:
▪ Increase (decrease) the room
temperature preset value. See
the user reference guide.
▪ Adjust the room temperature
schedule. See
"3.5 Schedules:
Example" [ 4 7].
Increase the desired leaving
water temperature in accordance
with the heat emitter type. See
"3.3.3 Room thermostat control -
Using the leaving water
pages" [ 4 6].
temperature home
Adjust the weather-dependent
curve. See the user reference
guide.
Corrective action
If you immediately need domestic
hot water, activate the DHW tank
booster mode. However, this
consumes extra energy. See
"3.4.5 Using the DHW tank
mode" [ 4 7].
booster
If you can wait, overrule
(increase) the active or next
scheduled desired temperature
so that more hot water will be
produced exceptionally. See
"To
read out and overrule the active
or next scheduled desired
temperature (in scheduled mode
or scheduled + reheat
mode)" [ 4 7].
If the problem recurs daily, do
one of the following:
▪ Increase
the
DHW
tank
temperature preset value. See
the user reference guide.
▪ Adjust
the
DHW
tank
temperature
schedule.
Example:
Program
to
additionally
heat
up
the
DHW tank to a preset value
(Storage
eco = lower tank
temperature) during the day.
See
"3.5
Schedules:
Example" [ 4 7].
6.4
Symptom: Heat pump failure
When the heat pump fails to operate, the backup heater can serve
as an emergency heater and either automatically or non-
automatically take over the heat load.
▪ When auto emergency is activated and a heat pump failure
occurs, the backup heater will automatically take over the heat
load.
▪ When auto emergency is not activated and a heat pump failure
occurs, the domestic hot water and space heating operations will
stop and need to be recovered manually. The user interface will
then ask you to confirm whether the backup heater can take over
the heat load or not.
When the heat pump fails,
will appear on the user interface.
Possible cause
Heat pump is damaged.
INFORMATION
When the backup heater takes over the heat load,
electricity consumption will be considerably higher.
6.5
Symptom: The system is making
gurgling noises after
commissioning
Possible cause
There is air in the system.
Various malfunctions.
(a)
We recommend to purge air with the air purge function
of the unit (to be performed by the installer). If you purge
air from the heat emitters or collectors, mind the
following:
WARNING
Air purging heat emitters or collectors. Before you
purge air from heat emitters or collectors, check if an error
or
is displayed on the home pages of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to
purge air is sufficiently ventilated. Reason: Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
7
Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
7 Disposal
Corrective action
▪ Press
to view a description
of the problem.
▪ Press
again.
▪ Select
to allow the backup
heater to take over the heat
load.
▪ Call your local dealer to get
the heat pump fixed.
Corrective action
(a)
Purge air from the system.
Check if
is displayed on the
home pages of the user
interface. You can press
to
display more information about
the malfunction.
Operation manual
9