DS DS7445 설치 지침 - 페이지 2
{카테고리_이름} DS DS7445에 대한 설치 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. DS DS7445 2 페이지. Alpha-numeric lcd keypad
Volume Control
The keypad sounder volume can be adjusted using the [1] and [4]
keys along with the [*] key.
•
Hold the [*] key while pressing the [1] key to increase the volume.
•
Hold the [*] key while pressing the [4] key to decrease the volume.
NOTE: This only affects the keypad sounder. It will NOT affect the
alarm sounders/bells.
LCD Backlight Control
(DS7447 only)
•
Hold the [*] key while pressing the [3] key to increase the
brightness.
•
Hold the [*] key while pressing the [6] key to decrease the
brightness.
NOTE: After the Keypad Sounder Volume or Backlight has been
adjusted, you must arm then disarm the system once to store
this information in the control panel. If power is disconnected
before you arm the system, the settings will be lost.
Contrast Control
•
The keypad contrast can be increased by turning the contrast
control clockwise. To decrease the contrast, turn the contrast
control counterclockwise.
Special Emergency Key Labeling
(Do NOT label if unprogrammed)
If labeling, the unmarked key in the lower left corner of the keypad
MUST be labeled as the FIRE key because of its programming values
pre-set in the control panel. The unmarked center key should be labeled
as the Special Emergency key. The unmarked right key should be
labeled as the Panic key.
- See the graphics below:
Fire
Commercial Fire Applications
•
Single Keypad Use in Commercial Fire Systems:
The keypad must be used on the keypad bus and mounted to the
front of the control enclosure OR if within the same room as the
control equipment, with the wire run in conduit (or equivalently
protected against mechanical injury) within 20 ft. (6 m) of the control
equipment. The keypad must be assigned as keypad address 1.
•
Multiple Keypad Use in Commercial Fire Systems:
One keypad only must be used on the options bus and assigned
as keypad address 11-14. The keypad must be mounted to the
front of the control enclosure OR if within the same room as the
control equipment, with the wire run in conduit (or equivalently
protected against mechanical injury) within 20 ft. (6 m) of the control
equipment.
Detection Systems, Inc.
130 Perinton Parkway, Fairport, New York, USA 14450-9199
(585) 223-4060 • (888) 289-0096 • Fax: (585) 223-9180
R
B
G
Y
Contrast Control
Special
Panic
Emergency
(DS7400Xi Controls Only)
NOTE: Keypad 15 is not available on Commercial Fire Systems as
option bus address 15 is used for the DS7420i module.
NOTE: On the 7400xi Rev. 3+, a maximum of 11 keypads may be
used in Commercial Fire mode. One on the option bus and
up to 10 on the keypad bus.
•
Keypads 1-10 should be connected to the keypad bus and may
be placed as needed (within the wiring limits). One of these
keypads must be assigned as keypad address 1.
nstruction Label and Slide
I
An instruction label is provided and needs to be placed onto the pull-
out slide. The slide may be installed to pull from the left or the right
(slide it into rear of base). Be careful when installing the label; place it
as close to the pull-tab as possible.
Label
Slide in either side
(writing on other side)
In Case of Trouble
See the following chart:
Keypad Notification
DS7445
• The yellow and green wires have been
Continuous keypad
sounder
• The keypad has not been programmed
DS7447
Continuous keypad
sounder PLUS
• The control panel has malfunctioned.
"System Fault"
display
DS7445
Continuous keypad
sounder
• A keypad's address has not been set
DS7447
Continuous keypad
sounder PLUS
"Not Programmed.
See Instal Guide"
display
• Two or more keypads have the same
DS7445
address.
3 beep error tone on
all keypads
• DS7400 Series only: DS7430 MUX
module not installed on main board
DS7447
correctly. Check pin alignment.
3 beep error tone on
all keypads PLUS
• DS7400 Series only: Keypad and
"Entry Error. Please
another device on the option bus have
try again." display
the same address.
Label
Label
Possible Causes
disconnected.
properly at the control panel.
Replace the control panel.
with its address pins.
Copyright © 2002 Detection Systems, Inc.
DS7445/DS7447 Installation Instructions
P/N: 22235J 4/01