Daikin Clima-Flex CLIFC FIXED 400 설치, 운영 및 유지보수 매뉴얼 - 페이지 5

{카테고리_이름} Daikin Clima-Flex CLIFC FIXED 400에 대한 설치, 운영 및 유지보수 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Daikin Clima-Flex CLIFC FIXED 400 20 페이지.

Daikin Clima-Flex CLIFC FIXED 400 설치, 운영 및 유지보수 매뉴얼
CLIFC FIXED - INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Standard features

STRUCTURE
All F&C units are built with heavy gauge corrosion resistant galvanized steel. All units are approved for installation
with "0" clearance to combustible materia
MOTORS
Standard motors are PSC, permanently lubricated type with internal thermal overload protection.
PLENUM
Return air plenums are manufactured from galvanized steel insulated with high-density anti-bacterial and anti-acus-
tic foam.
CONDENSATE PANS
Positive sloped drain pans are galvanized steel, coated on the inside surface with anti-bacterial and anti- fungal
coating.
COIL
Constructed with seamless copper tubes and headers. The tubes are mechanically expanded into corrugated alu-
minum fin material for a permanent primary to secondary surface bond. Coils are tested under water at 350 PSI for
operation at 300 PSI. Coils include manual air vent
FAN WHEELS
Are double width, double inlet (DWDI) forward curved, centrifugal type. Wheels are statically and dynamically ba-
lanced for smooth, quite operation. The housing is constructed from heavy gauge galvanized steel with die-formed
inlet cones.
MOTORS
Motors are PSC, permanently lubricated type with internal thermal overload protection.
CLIMA-FLEX
5