When viewing menu tree options, the standard convention is:
Point Name (as listed on the HMI) [BACnet ID] R or R/W (read only or
read/write).
Example:
Space Temp [AV33] R

Main Display

Space Temp [AV33] R – Current space temperature at the User
Interface (or remote space temperature sensor if equipped).

Quick Access

Fan Command [MSV51] R/W – This is accessed by pressing the "up
arrow" from the main screen and is used to turn the unit ON and OFF. The
unit will cycle on and off to maintain space temperature by supplying the
temperature of air defined in the CONFIG menu.

Set Points

Mode [MSV53] R/W – This is the mode of operation. Select "Heat" or
"Vent" as desired (if the unit has cooling installed the choices will be "Heat/
Cool/Air")
Occ Set Point [AV51] R/W – Occupied Heat Set Point.
Unoc Set Point [AV52] R/W – Unoccupied Heat Set Point (only
available if the unit has scheduling as an option).
Burner Reset [MSV54] R/W – Burner reset command for use during
a burner lockout alarm. This is an "on/_on_" toggle selectable via the "up
arrow" button.

Status

Space Temp [AV33] R – Current space temperature at the User
Interface (or remote space temperature sensor if equipped).
Outside Temp [AV34] R – Current outside air temperature.
Discharge Temp [AV35] R – Current discharge air temperature.
Heat Command [AV32] R – Current command (0% - 100%) issued
to the burner for heat.

Menu Tree

010622