{카테고리_이름} Daikin McQuay 910121754에 대한 설치 및 유지 관리 데이터을 온라인으로 검색하거나 PDF를 다운로드하세요. Daikin McQuay 910121754 16 페이지. Digitally adjustable display sensor for water source heat pumps smartsource gs series; smartsource gt series; with microtech iii controls enfinity cch series; enfinity ccw series; enfinity vfc series; enfinity vfw series; enfinity lvc series; enfinity lvw
Optional Technician Adjustments
9 = Humidity Setpoint (HSP).
10 = Temperature Value & Humidity Setpoint.
11 = Temperature Setpoint & Humidity Setpoint.
12 = Temperature Value & Temp Setpoint & Humidity
Setpoint.
13 = Humidity Value & Humidity Setpoint.
14 = Temperature Value, & Humidity Value &
Humidity Setpoint.
15 = Humidity Value & Temperature Setpoint &
Humidity Setpoint.
16 = Temperature Value & Temperature Setpoint &
Humidity Value & Humidity Setpoint (WSHP
Default).
P11
Setpoint Button Lockout (Factory set to "0": Temp.
& Humidity Setpoint Enabled.
Note: Selections in P11 will impact Menu P10).
Both Temperature & Humidity Setpoints are enabled
0
(No Setpoint lockout, WSHP Units Only).
1
Humidity Setpoint Only is Enabled (Temperature
setpoint is locked out, WSHP Units Only).
2
Temperature Setpoint Only is Enabled (Humidity
setpoint is locked out).
Both Temperature & Humidity Setpoints are Disabled
3
(Full Setpoint lockout).
P12
Dehumidification Enable/Disable
nOH Dehumidification is Disabled (Factory default
for FCU Units).
HuA Dehumidification is Enabled (Factory default
for WSHP Units).
P13
Occupancy Button Enable/Disable (Factory set to
enabled "ObE").
ObE Occupancy Button Enabled (Factory default)
Obd Occupancy Button Disabled
P14
Firmware Version - XXX.X
P15 For Units with a BACnet or LonWorks
Communications Module
Setpoint Calibration Offset (Factory set to "0".)
•
"UP" to increase offset up to +100 will raise the
MicroTech III perceived set point from the sensor.
•
"DOWN" to decrease offset down to -100. This will lower
the MicroTech III perceived set point from the sensor.
Calibrate the displayed set point to the set point value sent
to the MicroTech III as follows:
Set the digital room sensor displayed set point to 90° F.
1.
2.
Observe the local set point via the BAS/EMS connected
by the BACnet or LonWorks Communications Module.
Adjust the Configuration Menu P15 on the sensor until
3.
the local set point and the displayed set point are equal.
P15 For Units without a BACnet or LonWorks
Communications Module
Setpoint Calibration Offset (Factory set to "0".)
•
"UP" to increase offset up to +100 will raise the
MicroTech III perceived set point from the sensor.
•
"DOWN" to decrease offset down to -100. This will lower
the MicroTech III perceived set point from the sensor.
The Setpoint Calibration Offset can be calculated using the
following formula:
ROUND [(Controller Vdd / Sensor Vdd )*1000]-1000
Example:
Given: Controller Vdd = 5.15VDC
Sensor Vdd = 4.95 VDC
The programmed Calibration Offset would be
[(5.15/4.95)*1000] -1000 = 40
IM 1171-3 / Page 13 of 16