DS Stoves Stoker 소유자 매뉴얼 - 페이지 12
{카테고리_이름} DS Stoves Stoker에 대한 소유자 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DS Stoves Stoker 17 페이지. High efficiency auger fed rice coal furnace
2. The Low Limit Setting: This turns off distribution blower when limit switch temperature drops
below this set point. (Only turns off distribution blower, stoker will still be able to run) Factory
setting is 100 degrees Fahrenheit.
3. The Middle Limit Setting: This turns distribution blower on when limit switch temperature rises to
set point. Distribution blower will stay on until limit switch temperature drops below the low limit set
point. (This only turns on distribution blower. It does not interrupt operation of stoker in any way) Factory
setting is 170 degree Fahrenheit.
• Loss of Draft: This can occur during hot, humid summer weather, with low fire in burner.
Changing the number of minutes of run time per half hour, increasing slightly the coal feed and air set-
tings may help. Thoroughly clean the furnace flue pipe and chimney. Remove fly ash buildup in furnace
by removing clean out plates and removing fly ash from furnace. Check to make sure all openings that
could infiltrate air from furnace base are sealed either by gaskets or seal it right caulk.
• Too much Draft: This is most likely to happen during cold, windy weather where there is no baro-
metric damper installed in chimney pipe. In this situation the fire continues to burn, even though the
stoker is not on. Adding a barometric damper and or properly adjusting barometric damper can help.
Adjust barometric damper so that you have about a negative .05 or negative .06 inches of water column
in your single wall chimney connector between your barometric damper and where single wall chimney
connector enters the furnace. Exhaust fans can also cause this problem by drawing air down the chim-
ney, through the burner and out of the housing inlet. This can be corrected by providing adequate out-
side air openings for both the stoker and the exhaust fan or discontinuing the use of exhaust fan.
Cleaning and Maintenance
• Turn off all power supply or disconnect power cord before attempting any maintenance.
• We recommend that you completely clean out stoker pot immediately after unit is shut off and
cooled down for the summer. Take auger out of auger pipe and completely clean out left over coal, this
will help reduce corrosion. Spray full inside with vegetable oil. If furnace is located in a damp
atmosphere it is recommended to put heat lamp inside furnace to reduce corrosion while furnace is not
running.
• Clean out fly-ash every 1,000 hours or at least once annually. You can expect fly-ash buildup
behind baffle in the base of unit and under pot rings. (remove pot rings once annually to remove fly ash.)
Remove all clean out plates from furnace, (including pot insert clean out on bottom of pot assembly) and
remove fly-ash with ash-vac or by just cleaning out manually. Also remove single wall chimney connec-
tor from furnace and remove fly-ash. There may be some fly-ash buildup in the single wall chimney
connector elbow.
• Check all gaskets and sealer joints for cracks or leaks annually. Replace gaskets or seals as
needed.
Coal
1. Use rice sized coal in your stoker furnace. With not more than 10% oversize and not more than
15% under size. Not following these guide lines will result in poor combustion.
2. Avoid using wet coal, this will retard combustion and increase carbon monoxide output.
12