Daintree GE Current WFA100-SN 설치 매뉴얼 - 페이지 5
{카테고리_이름} Daintree GE Current WFA100-SN에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Daintree GE Current WFA100-SN 11 페이지. Wireless fixture adapter
Daintree
Networked Wireless Fixture Adapter (WFA100-SN)
®
3
Wiring Continued
This configuration allows the WFA100-SN to provide automatic
0-10V dimming control and to switch ballasts On/Off. It also
provides an analog photosensor input (0-10V). Remove the
jumper from the violet and gray terminals before connecting
the 0-10V dimming control wires.
Figure 8: Dimming Ballast(s), Photosensor configuration
Figure 5: On/Off (non-dimming) Ballasts
This configuration allows the WFA100-SN to provide automatic 0-10V
dimming control and to switch ballasts On/Off. It also provides an
occupancy sensor input. Set occupancy sensor for minimum time
delay. Remove the jumper from the violet and gray terminals before
connecting the 0-10V dimming control wires. Remove the jumper
from the blue and gray terminals before connecting the occupancy
sensor wires.
Figure 9: Dimming Ballast(s), Photosensor, Occupancy
Sensor configuration
Perform Installation Test Suite 3
Perform Installation Test Suite 4
5
Installation Guide