DSC PowerSeries PC1832 설치 매뉴얼 - 페이지 13
{카테고리_이름} DSC PowerSeries PC1832에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DSC PowerSeries PC1832 20 페이지. System
enhancement
module
DSC PowerSeries PC1832에 대해서도 마찬가지입니다: 설치 매뉴얼 (17 페이지), 설치 매뉴얼 (13 페이지), 매뉴얼 (18 페이지)
LEDs
The Alarm.com Module LEDs can be used to indicate communication
errors, panel communication, network communication, and signal strength.
BOTTOM OF ALARM.COM MODULE
LED
FUNCTION
L1
Error LED: L1 will flash 1 to 8 times in a four-second interval
to indicate specific error conditions such as a network error,
panel communication error, or radio error.
L2
Panel communication LED: L2 flashes every time a data
packet is received from the panel.
L3
Cellular communication LED: L3 flashes every time a data
packet is received from the cellular radio.
L4
Cellular signal level LED: L4 flashes 0 to 5 times indicating
the cellular signal strength, or toggles on/of f when
communicating with the Alarm.com servers.
L5
Z-Wave Error LED: Visit the Dealer Website Support
Resources for additional Z-Wave installation resources.
LED L1 (RED)
L1 flashes when an error is encountered. The number of flashes indicates
the error number. If there are two or more errors at the same time, the
errors will flash one after the other. The LED will stay off for at least four
seconds between errors.
LED L1 ERROR DESCRIPTIONS AND SOLUTIONS
1
Alarm.com module cannot communicate with the panel.
Perform a power cycle on the panel. If the error persists
lift the Alarm.com module out of the SEM circuit board and
re-insert it, while power is disconnected from the system.
2 then 4
The Alarm.com module provisioning process could not be
completed. If the error persists, power cycle the system,
then contact Technical Support.
2 then 5
The Alarm.com module provisioning process could not be
completed because the module is currently roaming off the
carrier's primary network.
3
The Alarm.com module is trying to register on the cellular
network. If it persists for more than a few minutes, the
module is having problems registering. Check L4 for signal
level. If signal level is lower than 2 bars, change the panel's
location or use a remote antenna option.
System
Enhancement
Module (SEM)
2
1
13