DSC Meridian MN-220RT 설치 및 사용 지침 - 페이지 3

{카테고리_이름} DSC Meridian MN-220RT에 대한 설치 및 사용 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. DSC Meridian MN-220RT 4 페이지. 2-wire

1 Every family member should participate in developing the escape
plan.
2 Study the possible escape routes from each location within the
house. Since many fires occur at night, special attention should be
given to the escape routes from sleeping quarters.
3 It is essential that escape from a bedroom be possible without
opening the interior door. Consider the following when making
your escape plans:
• Make sure that doors and windows that open to the outside are
easily opened. Ensure that they are not painted shut, and that their
locking mechanisms operate smoothly.
• If opening the exit or using the exit is too difficult for children, the
elderly or handicapped, plans for rescue should be developed.
This includes making sure that those who are to perform the rescue
can promptly hear the fire warning signal.
• If the exit is above the ground level, an approved fire ladder or rope
should be provided, as well as training in its use.
• Exits on the ground level should be kept clear. Be sure to remove
snow from exterior patio doors in winter; outdoor furniture or
equipment should not block exits.
• The family should have a predetermined assembly point where
everyone can be accounted for; for example, across the street or
at a neighbour's house.
• Once everyone is out of the house, call the Fire Department.
• A good plan emphasizes quick escape. Do not investigate first or
attempt to fight the fire, and do not attempt to rescue belongings
or valuables as this takes up time. Once outside, do not re-enter
the house; wait for the Fire Department.
• Write the plan down and rehearse frequently so that should an
emergency arise, everyone will know what to do. Revise the plan
as conditions change; for example, when there are more or fewer
family members in the home, or if there are changes to the house.
• Make sure your fire warning system is operational by conducting
weekly tests. If you are unsure about system operation, contact
your Smoke Detector Installer or Dealer.
• It is recommended that you contact your local fire department and
request further information on home fire safety and escape planning.
If available, have your local fire prevention officer conduct an in-
house fire safety inspection.
Installation Instructions
Specifications
Nominal Operating Voltage ...................... 12 - 24VDC or VFWR
Maximum Operating Voltage Range ................. 10 - 30VDC, or
.............................................................................. 10 - 26.4VFWR
MN220
MN220T
MN220R
MN220RT
MN220 Series Compatiblity Identifier: ............................. PS220
Compatible Control Units:
DSC PC5010 with compatibility identifier: ....................... PC5-1
Maximum no. of detectors per zone: ..................................... 30
Min. detector voltage/current
to operate relay (MN220R, MN220RT): ................. 7.5VDC/35mA
Auxiliary Relay Rating (Resistive)
Form C Relay ............................................... 2A at 30VDC / VAC
Temp Sensor .................................................... 57
Smoke Sensitivity .................... 2.0%/ft obscuration ±0.6%/ft (UL)
Operating Environment ....................... 0°C - 50°C (32°F - 100°F)
.................................................. 5% - 93% RH, non-condensing
Dimensions
Mounting the Unit
Standby Current
@12V
@24V
15µA
50µA
25µA
60µA
15µA
65µA
30µA
75µA
Wiring
o
C (135°F) fixed
**
Field Test .................................. Magnet-activated switch and/or
...................................... Gemini 501 Smoke Alarm Analyser**
Test Button &
Alarm Indicator
The
Meridian
Smoke
Detector
mounts
to
a
standard
4"
octagonal
electrical box. 12 to 24V
DC
or Full Wave Rectified
power must be supplied
from a UL/ULC-listed alarm
control unit. Wiring should
be in accordance with the
appropriate
national
electrical
code
and
applicable local codes.
Remove the mounting plate
from the case by pushing the locking tab and turning the mounting
plate counter-clockwise. Attach the mounting plate to the electrical
box (see diagram above for orientation).
THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH
THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD
72. (National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269)
Refer to the wiring diagrams on this installation sheet and those
provided in the Installation Manual of the alarm control panel being
used with the unit.
Before connecting the unit, prepare the wires from the electrical box
for connection; the wires should not be frayed or bent.
CAUTION: If the power connections are reversed, the unit will
not operate. The unit is protected against damage from incorrect
wiring.
Gemini Scientific, 1122B Aster Ave., Sunnyvale, CA 94086 Tel: 408-554-0310
2.0"
51 mm
Locking Tab
Form C Aux. Relay wires
dress through this opening
Mounting
Holes
THIS SIDE OUT
Power and Form A Relay wires
dress through this opening
Smoke Detector Mounting Plate
5.13"
131 mm