DSE DSE8610 MKII 설치 지침 매뉴얼 - 페이지 2
{카테고리_이름} DSE DSE8610 MKII에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DSE DSE8610 MKII 2 페이지.
DSE DSE8610 MKII에 대해서도 마찬가지입니다: 설치 지침 (2 페이지)
MAIN CONFIGURATION EDITOR PARAMETERS
NOTE: Depending upon module configuration, some values in the may not be
available. For more information refer to DSE publication 057-239 DSE8610 MKII
Configuraiton Suite PC Software Manual available from www.deepseaplc.com
Section
Parameter As Shown On Display
Values
Display
Contrast
0%
Language
English, Other.
Current Date and Time
hh:mm
Engine
Oil Pressure Low Shutdown
0.00 bar
Oil Pressure Low Pre Alarm
0.00 bar
Coolant Temp high Pre Alarm
0 ºC
Coolant Temp High Shutdown
0 ºC
Start Delay Off Load
0h 0m 0s
Start Delay Telemetry
0h 0m 0s
Engine Pre Heat Timer
0h 0m 0s
Engine Crank Duration
0h 0m 0s
Engine Crank Rest Time
0h 0m 0s
Engine Safety On Delay
0h 0m 0s
Engine Smoke Limiting
0h 0m 0s
Engine Smoke Limiting Off
0h 0m 0s
Engine Warm Up Time
0h 0m 0s
Engine Cool Down Time
0h 0m 0s
Engine Speed Overshoot Delay
0h 0m 0s
Engine Speed Overshoot
0h 0m 0s
Engine Failed To Stop Delay
0h 0m 0s
Battery Under Voltage Warning
Active / Inactive
Battery Under Voltage Warning Delay 0h 0m 0s
Battery Under Voltage Warning
0 V
Battery Over Voltage Warning
Active / Inactive
Battery Over Voltage Warning Delay
0h 0m 0s
Battery Over Voltage Warning
0 V
Charge Alternator Failure Warning
Active / Inactive
Charge Alternator Failure Warning
0 V
Charge Alternator Warning Delay
0h 0m 0s
Charge Alternator Failure Shutdown
Active / Inactive
Specific Gravity
0.80 to 1.00
CAN Termination
Active / Inactive
Generator
Under Voltage Shutdown
0 V
Under Voltage Pre-Alarm
0 V
Loading Voltage
0 V
Nominal Voltage
0 V
Over Voltage Pre-Alarm
0 V
Over Voltage Shutdown
0 V
Under Frequency Shutdown
0 Hz
Under Frequency Pre-Alarm
0 Hz
Loading Frequency
0 Hz
Nominal frequency
0 Hz
Over Frequency Pre-Alarm
0 Hz
Over Frequency Shutdown
0 Hz
Full Load Rating
00 A
kW Overload Trip
0 %
Delayed Over current
Active / Inactive
Gen Over Current Trip
0 %
AC System
3 Phase 4 Wire
CT Primary
0 A
CT Secondary
0 A
Short Circuit Trip
0 %
Earth CT Primary
0 A
Earth Fault Trip
Active / Inactive
Earth Fault Trip
0 %
Transient Delay
0h 0m 0s
Gen Reverse Power Delay
0h 0m 0s
Full kW Rating
0 kW
Full kVAr Rating
0 kvar
Load Ramp Rate
0 %
Load Level For More Sets
0 %
Load Level For Less Sets
0 %
MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED)
Section
Parameter As Shown On Display
Generator
Load Demand Priority
(Continued) Gen Reverse Power
Insufficient Capacity Delay
Insufficient Capacity Action
Reactive Load CTL Mode
Load Parallel Power
Load Power Factor
Enable MSC Compatibility
Timers
LCD Page Timer
Scroll Delay
Engine Pre Heat Timer
Engine Crank Duration
Engine Crank Rest Time
Engine Safety On Delay
Engine Smoke Limiting
Engine Smoke Limiting Off
Engine Warm Up Time
Engine Cool Down Time
Engine Speed Overshoot Delay
Engine Failed To Stop Delay
Battery Under Voltage Warning Delay 0h 0m 0s
Battery Over Voltage Warning Delay
Return Delay
Generator Transient Delay
Scheduler
Scheduler
Schedule On Load
Schedule Period
Schedule Time & Date Selection (1-
16)
DIMENSIONS AND MOUNTING
DIMENSIONS
245 mm X 184 mm X 51 mm
(9.6" X 7.2" X 2.0")
WEIGHT
0.98 kg
(2.16 lb)
Power Cycle After Exit
Power Cycle After Exit
Values
1
0 kW
0h 0m 0s
None / Indication / Warning /
Shutdown / Electrical Trip
None / VAr Share
0 kW
In Mains Parallel Mode
0 %
In Mains Parallel Mode
Active / Inactive
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
0h 0m 0s
Active / Inactive
Active / Inactive
Weekly, Monthly
Press
to begin editing then
or
when selecting the
different parameters in the
scheduler.
PANEL CUTOUT
220 mm X 160 mm
(8.7" X 6.3")
TEMPERATURE
Operating: -40 ºC to +70 ºC
(-40 ºF to +158 ºF)
Storage: -40 ºC to +80 ºC
(-40 ºF to +176 ºF)
ACCESSING THE 'RUNNING' CONFIGURATION EDITOR
•
The 'running' editor can be entered while the engine is running. All protections
remain active if the engine is running while the running editor is entered.
•
Press and hold the
(Tick) button to enter the running editor.
RUNNING CONFIGURATION EDITOR PARAMETERS
Section
Parameter As Shown On Display
Display
Contrast
Language
Load Demand Priority
Load Power Factor
Load Parallel Power
)
Commissioning Screens
Override Starting Alarms
Voltage Adjust
(manual mode only engine running breaker open)
Frequency Adjust
(manual mode only engine running breaker open)
REQUIREMENTS FOR UL CERTIFICATION
WARNING!: More than one live circuit exists, see diagram overleaf for further
information.
Specification
Description
Screw Terminal
• 4.5 lb-in (0.5 Nm)
Tightening Torque
• Terminals suitable for connection of conductor size 13 AWG
Conductors
to 20 AWG (0.5 mm² to 2.5 mm²).
• Conductor protection must be provided in accordance with
NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the
engine starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit
conductors shall be separated and secured to maintain at
least ¼" (6 mm) separation from the generator and mains
connected circuit conductors unless all conductors are rated
600 V or greater.
• Must be connected through UL Listed or Recognized isolating
Current Inputs
current transformers with the secondary rating of 5 A max.
• Must be connected to communication circuits of UL Listed
Communication
Circuits
equipment
• 0.5 A
DC Output Pilot Duty
• Suitable for flat surface mounting in Type 1 Enclosure Type
Mounting
rating with surrounding air temperature -22 ºF to +122 ºF (-30
ºC to +50 ºC)
• Suitable for pollution degree 3 environments when voltage
sensing inputs do not exceed 300 V. When used to monitor
voltages over 300 V device to be installed in an unventilated
or filtered ventilation enclosure to maintain a pollution degree
2 environment.
Operating
• -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Temperature
Values
0 %
English, Other
1
0 %
0 %
Active / Inactive
Active / Inactive
0 %
0 %