ATTACK FD boiler is a cast iron low-pressure boiler for combustion of solid fuels - coke, wood, coal:
Combustion of other substances like plastics is not allowed..
1. The use and preferences of the boiler
Four-element size of ATTACK FD is suitable for reconstructions of heat sources in dwellings, for smaller flats and recreation
facilities. Bigger size of the boiler suits to requirements for heating in family houses, shops, schools and similar..
The boiler is produced as a hot-water boiler with natural as well as forced heating water passage and working overpressure up to
4 bar. Before delivery it is tested for tightness by a testing overpressure of 8 bar.
Boiler preferences :
Modern design
High lifetime of cast iron heat exchanger, with extra low-temperature corrosion resistance
High efficiency up to 85%
Wide output range in dependance on number
of elements
5-years warranty on the cast iron heat exchanger
High reliability of regulating and safety components
Simple attendance and maintenance
Simple assembly of casing during the boiler assembly in the boiler room
Low demand on chimney draught
Good position of the output regulator
Enlarged combustion chamber for bigger wood pieces
Sophisticated production technology with a stable and verified quality of production process( ISO 9001)
2. Technical parameters of ATTACK FD
Boiler type
Elements number
Nominal output - coke
Fuel consumption at nominal output-coke
minimum output - coke
Fuel consumption at minimum output - coke
Nominal output - black coal
Fuel consumption at nominal output - black coal
minimum output - black coale
Fuel consumption at minimum output - black coal
Nominal output - wood
Wood consumption at nominal output
minimum output - wood
Wood consumption at minimum output
Capacity of combustion chamber
Boiler water volume
Max. working pressure
Weight
Height P
Height
Width
Depth L
Lenght of combustion chamber
Width of combustion chamber
Dimensions of door (width x height)
Efficiency
Test pressure
Connection of C.H. water
Connection of cooling loop
Burning time at nominal output - black coal
Burning time at nominal output - wood
Max.lenght of logs at max. diameter of 150 mm
Operation drauhgt at min. and nom.output
Flue gas temperature at nom. output
Flue gas flow- nom. output
Flue gas temperature at min. output
Flue gas flow- min. output
FD20
pcs
4
kW
20
kg/h
3,7
kW
6
kg/h
1,11
kW (kcal/h)
18 (18000)
kg/h
3,6
kW
9
kg/h
1,9
kW
16
kg/h
4,85
k W
8
kg/h
2,15
3
dm
25,5
l
27
bar
kg
210
mm
mm
mm
mm
455
mm
290
mm
mm
%
bar
inch
inch
h
h
mm
280
Pa
10-20
°C
240
g/s
9,54
°C
120
g/s
3,02
4
FD26
FD32
5
6
2 6
32
4,8
5 ,9
8
9 ,5
1,48
1 ,76
24 (22000)
3 0 (26000)
4,6
5 ,2
12
15
2 ,3
2 ,6
20
25
6,11
7,38
10
13
2,52
2,89
34
42,5
31
35
4
245
2 80
1081
1001
4 70
555
655
390
490
3 00
230 x 310
78-82
8
G 2"
G 1/2inner thread
4
2
380
480
12-22
13-23
250
250
12,31
15,08
130
140
3,95
4,66
FD36
FD42
7
8
3 6
42
6,66
7,77
11
12,5
2,04
2 ,31
3 6(30000)
42(34000)
6,4
7,5
18
21
3,2
3 ,7
30
34
8,65
9,92
15
17
3,26
4,63
51
59,5
39
43
315
350
755
855
590
690
580
680
15-25
18-28
260
260
16,99
19,78
150
150
5,36
6,04