7. Application Examples
1) Use DSPR310D under single step mashing mode (similar to DSPR300)
Set the parameter as following:
Under PROG menu, set C – 1 as your mash temperature (like 122F), t – 1 to a
large time like 99:00; set all unused t – 2 ~ t – 6 to 00:00. Under MASH menu,
set EO to OFF.
Once powered up, this controller will maintain at the temperature of C – 1 for a
long time. You can manually end this process by press and hold Key B, of simply
turn off the controller.
2) Use DSPR310D as a manual power regulator (similar to DSPR1)
Set the parameter as following:
Mode = boil, tF = off, bAST = 0
To use it as manual regulator with temperature reading, please set it to boiling
mode. Disable timer event, and set boiling acceleration set temperature below
ambient temperature (or just zero).
8. Wiring Examples
Example 1. Here are two wiring diagrams of how to connect a DC triggered AC
SSR with this power regulator.
2018.08
Press
80
End
100
Press
Knob
Press
ap2
Alarm 2
5
pulse length
Press
Knob
Press
Press
Alarm 1
ap1
pulse length
5
Knob
Press
Press
Alarm 1
hy1
hysteresis band
0.3
Press
Knob
Press
al1
Knob Press
off
Alarm 1
low limit
Figure 13. Wiring examples of controlling a heater with SSR and DSPR310D in
a 120VAC system (upper) and in a 240VAC system (lower).
Example 2. Here is the wiring diagram of how to wire two external buzzers to
the controller.
N
120VAC
120VAC
buzzer
buzzer
L
R
RTD
R
W
Figure 15. Wiring example of external buzzers. Power supply for the controller
and heater is 240V AC. Power supply for two buzzers is 120V AC. AL1 buzzer
is for absolute temperature alarm. AL2 buzzer is for step alarm.
9. Beeping sound definition:
The pattern of the beeping sound for each condition is different. This section will
help user to tell what is the beeping for:
Legend:
―
1s short beep
――
2s long beep
―――――
5s long beep
●
1s short pause
●●
2s long pause
Step mashing mode:
1) Four 2s long beeps (―― ● ―― ●● ―― ● ――): It is separated by a 1s
short pause, a 2s long pause and another 1s short pause. It indicates that
current step is finished. Starting to heat up for the next step.
2) Three 1s short beeps (― ● ― ● ―): It indicates that the current mashing
step has started. The reading temperature has reached timer starting set point.
3) Eight 5s long beeps (――――― ●● ――――― ●● ―――――
●● ――――― ●● ――――― ●● ――――― ●● ―――――
●● ―――――): It indicates the whole program has ended. Both display will
flash "end".
Boiling mode:
1) Four 2s long beeps (――●―― ●● ――●――): It is separated by a 1s short
pause, a 2s long pause and another 1s short pause. It indicates that timer has
WWW.AUBERINS.COM
4
+