Auber Instruments TH100ACHIMDX 사용 설명서 - 페이지 2

{카테고리_이름} Auber Instruments TH100ACHIMDX에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Auber Instruments TH100ACHIMDX 2 페이지. Thermometer for stove pipe, chimney, w/ remote alarm

AUBER INSTRUMENTS
Note 2. Set alarm for internal buzzer
The meter offers two alarms that can be set to turn on the internal buzzer at specific
temperatures. The first alarm is controlled by parameters AH1 and AL1. The initial
setting will turn on the buzzer at 481 ° F and off when temperature drops below 480° F.
The second alarm is controlled by parameters AH2 and AL2. The initial setting of the
second al a rm is deactivated. It can be set as low alarm to send warning.
AH1 and AH2 are the temperatures to turn the inernal buzzer on; AL1 and AL2 are the
temperatures to turn buzzer off. When AH1(2) >AL1(2), the alarm is set for absolute
high alarm as shown in Figure 4 below. When AH1(2) <AL1(2), the alarm is set for
absolute low alarm as shown in Figure 5 below. When AH1(2)=AL1(2), the alarm is
deactivated.
Example, if AH1=481, AL1=480, when the temperature goes up to 481° F, the buzzer
will be on; when the temperature drops down to 480° F, the buzzer will be off. If
AH2=180, AL2=185, when the temperature drops down to 180° F, the buzzer will be
on; when the temperature goes up to 185° F, the buzzer wil l be off.
User can press the shift key (>) to temporarily mute the buzzer sound. The alarm will
buzz again if the alarm set temperature is reached again. To permanently deactivate
the alarm, set AH1=AL1 or AH2=AL2. Please see flow chart in Figure 3 on how to set
the value.
The default setting is both internal and external buzzer are on when the
temperature is above 481 (SV+Hy, AH1); will be off when the temperature drops
down to 480 (SV, AL1).
PV
Buzzer on
Figure 4. Absolute high alarm
5.2 System Configuration Parameters (accessed by code 0089)
Table 3. System configuration parameter setti n g
Code
Description
inty
Input Sensor Type
Inty
Output Mode
outy
outy
Hy
Hysteresi s Band
hy
atdu
Atdu
Ignore thi s setting
psb
Input Offset
PSb
rd
External alarm type
rd
Display Unit
corf
CorF
Exit
end
End
Parameter Display
Oper ation Mode
Enter Code
SET
SET
0089
XXXX
SET
Figure 6. The system setup flow chart
Note 3. The value of outy should be 3.
Note 4. The default setting for the external buzzer is high limit alarm. The external
b u z z er w i l l be on when the tempeature is above SV+Hy will be off when the
temperature drops back to SV. The default setting for the Hy is 1.
2013.05
PV
Buzzer on
Figure 5. Absolute low alarm
Setting Range
Initial
See Appendix
K
0, 1, 2, 3, 4, 5, 6
Note 3
3
0~9999
1
Note 4
0~200
-1000~1000
Note 5
0
0: low 1: high
Note 6
1
Note 7
° C 1:° F
0:
1
inty
Output mode selection
SET
SET
X
outy
Hysteresis Band
SET
SET
XXXX
HY
Autotune offset
SET
SET
X
atdu
Input offset
SET
SET
XXXX
psb
Heating/Cooling
SET
SET
X
rd
Display Unit(C/F)
SET
SET
X
corf
end
Note 5. Calibration offset, PSb is used to set an input offset to compensate the error
produced by the sensor. For example, if the meter displays 5 º C when probe is in
ice/water mixture, setting PSb= -5, will make the controller display 0 ºC.
Note 6. Rd is for system function selection, Its value should be kept as 1 for high limit
alarm.
Note 7. Display unit selecti o n CorF: 0 for Celsius (° C); 1 for Fahrenheit (° F).
Additional note:
The remote alarm control output of this thermometer can also be used as a PID or
on/off control output. For detail s , please refer to Auber SYL-1614 manual.
Note
5755 North Point Parkway, Suite 99
Alpharetta, GA 30022 USA
Tech support: 770-569-8420, 404-983-8228
Copyright 2007-2016, Auber Instruments All Rights Reserved.
No part of this manual shall be copied, reproduced, or transmitted in any way
without the prior, written consent of Auber Instruments. Auber Instruments
retains the exclusive rights to all information included in this document.
WWW.AUBERINS.COM
Auber Instruments, Inc
P2/2