Auber Instruments SYL-53X2P 보충 설명서 - 페이지 3

{카테고리_이름} Auber Instruments SYL-53X2P에 대한 보충 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Auber Instruments SYL-53X2P 5 페이지.

AUBER INSTRUMENTS
Table 3.3 Status parameters (read only)
Note*: Parameter Data Type
Some parameters in this controller may display in decimal number (number with one decimal digit) rather than integral number. For example, your
display temperature can be 20.1 degree (decimal number) and your step 2 ramp timer is 10 minutes (integral number). For decimal number, its
actual stored value in controller's memory will be 10 times larger than its display value. For example, if your display temperature is 20.1, it will be
stored as 201 (Decimal) or C9 (Hex) in its register. For integral number, its actual stored value in the controller's memory will be the same as its
display value.
This controller uses signed 16-bit number and it cannot read floating point numbers.
Note**: Input Sensor Type
This PID controller can read the following 9 different temperature sensor types. Please find the table below. Sn code is the Sn value used in its
software. Sn symbol is the display value on the PID controller.
Note***: Alarm Status
This parameter shows the status of both AL1 and AL2 relay outputs. See table below:
2020.09
Description
Data Type*
Reading Temp
Decimal
Current Set Temp
Decimal
Main Output (0-200%)
Integral
Alarm Status***
Integral
Table 3.4 Value table for input sensor type
Sn Code
Sn Symbol
0
CU50
1
PT1
2
PT2
3
K
4
E
5
6
T
7
S
8
R
Table 3.5 Value table for alarm status
Value
0
1
2
3
Register Absolute Address
Holding Register Address
1001
1002
1101
1201
Definition
Cu50 (RTD)
Pt100 (RTD), -200~200C
Pt100 (RTD), -200~600C
K (thermocouple)
E (thermocouple)
J
J (thermocouple)
T (thermocouple)
S (thermocouple)
R (thermocouple)
Alarm status
AL1 OFF, AL2 OFF
AL1 ON, AL2 OFF
AL1 OFF, AL2 ON
AL1 ON, AL2 ON
WWW.AUBERINS.COM
44098
44099
44354
44610
P3/5