3.3 Control Circuits
WARNING
Isolate the CSX completely from the power supply before attempting any work on
the CSX or motor. Control terminals may be at phase voltage potential.
AVERTISSEMENT
Isoler complètement le CSX de l'alimentation secteur avant de tenter toute
intervention sur le CSX ou sur le moteur. Les bornes de commande peuvent être
au potentiel de la tension de phase.
CAUTION
For CSX-xxx-xx-C2 (24 VAC/VDC control voltage) units you can connect an
external 24 VDC supply into the control input terminals 01, 02.
110-240 VAC
&
24 VAC/VDC
380-440 VAC
Start/stop. To reset a trip, open then close 02.
Start.
Stop. To reset a trip, open then close 02.
3.4 Outputs
Main Contactor Output
The Main Contactor output (terminals 13, 14) closes as soon as the soft starter receives a
start command and remains closed while the soft starter is controlling the motor (until the
motor starts a coast to stop, or until the end of a soft stop). The Main Contactor output will
also open if the soft starter trips.
The Main Contactor output can be used to directly control a main contactor coil.
Run Contactor Output
The relay (terminals 23, 24) operates four seconds after the set start ramp time is complete.
The relay can be used to operate a contactor for power factor correction capacitors, or to
signal soft starter run status to an automation system.
710-02407-00J
Two-wire control
A3
A1 (+)
A2 (-)
01
1
02
A3
A1
A2
01
1
02
CSX User Manual
ELECTRICAL INSTALLATION
Three-wire control
A3
A1 (+)
A2 (-)
2
01
3
02
A3
A1
A2
2
01
3
02
5