Duco DucoBox Focus 설치 매뉴얼 - 페이지 12
{카테고리_이름} Duco DucoBox Focus에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Duco DucoBox Focus 16 페이지.
Duco DucoBox Focus에 대해서도 마찬가지입니다: 사용자 설명서 (2 페이지), 설치 매뉴얼 (20 페이지), 빠른 시작 (4 페이지)
ENGLISH
07 Air calibration
For the system to work correctly, it needs to be configured� This will ensure its operation is as quiet as possible and energy-ef-
ficient� For information on determining the ventilation flow rates, see Instruction Sheet Checking Product References and Flow
Rates at www�duco�eu�
07.A Air calibration procedure for DucoBox Focus
The air calibration procedure must be carried out on a calm day (no more than wind force 2: leaves rustling,
feeling the wind in one's face)�
DucoBox Focus air calibration
The exhaust vents must be set depending on the situation� Proper pre-setting makes for rapid and correct configuration�
1
SITUATION 1 :
one vent per valve
Set all vents to the fully open
position, regardless of the desired
flow rate�
When using DucoVent Design exhaust vents always leave
the outer ring in place for acoustic effect�
12
L2000631 Installation guide for DucoBox Focus (Revision L | 06.09.2022)
SITUATION 2 :
Multiple vents per valve
with equal flow rates
Set all vents to the fully open
position, regardless of the desired
flow rate� Set the valve to the
sum of the vent flow rates via the
display menu or the Duco Network
Tool� Example: 2 vents, 50 m³/h
each → set valve to 100 m³/h�
+
=
m
Flow rate
75m3/h
50m3/h
25m3/h
SITUATION 3 :
Multiple vents per valve
with different flow rates
Set the exhaust vents so they
match the desired flow rate in line
with the table below� Set the valve
to the sum of the vent flow rates
via the display menu or the Duco
Network Tool� Example: 25 m³/h
vent and 75 m³/h vent → set valve
to 100 m³/h�
+
100
/h
3
DucoVent
DucoVent Basic
Design
and other vents
=
100
m
/h
3
100% open
50% open
25% open