WALL MOUNTING

Follow Compressed Gas Association, OSHA and all applicable local codes. Manifolds should not be
placed in locations where the temperature will exceed 102°F (49°C) or fall below 0°F (-18°C). Manifolds
installed in open locations should be protected from weather conditions. During winter, protect the
manifold from ice and snow. In summer, shade the manifold and cylinders from continuous exposure
to direct sunlight. Always leave access to the manifold for cylinder replacement.
1. Determine and mark the vertical center line for installation of the AutoSwitch Console.
(Figure 3).
2. Measure from the floor 73" in height* of this center line. This height will place the manifold
header approximately 66" from the floor. Using a level, mark a horizontal line at this point
extending approximately 10 inches to the left and right of center.
3. Remove the mounting bracket from the rear of the AutoSwitch Console by removing the
retaining nuts at the bottom of the mounting bracket (Figure 5). Place the upper edge of
the bracket cross-member on the horizontal line so that it is centered with the vertical line.
Holding the bracket with the slotted extensions away from the wall, mark the location of the
two mounting bolts (Figure 4)
4. Using appropriate hardware based on wall construction, anchor the mounting bracket to the
wall (Figure 4).
5. Place the autoswitch system so that the mounting bracket slots align with the shoulder nuts.
With the autoswitch box hanging on the shoulder nuts, align the retaining bolts so that they
protrude through the bracket. Replace the mounting nuts that were removed in step 3.
Figure 3 - Center-line Mark
Console
Figure 5 - Console and Mounting Bracket
Mounting Screws
Figure 4 - Mounting Bracket
5
Shoulder Nuts
Mounting Bracket
Retaining nuts