The seat adjusting screw is nylon; care should be taken to avoid stripping
the threads when tightening the locknuts.
Removal From Service
a. Shut off valves upstream of regulators.
b. Open torch valves to bleed system before closing the regulator.
This will ensure regulator is drained before repressurizing.
c. Shut off regulators by turning the regulator adjusting screws coun-
terclockwise.
d. Remove Gas Mizer from system.
SERVICE
Send faulty equipment to a CONCOA-designated repair center for re-
pairs. Special tools and techniques are required to repair such equipment.
Personnel with experience with such equipment should perform repairs.
Shut off gas supplies at source before attempting inspection or service unless
leak testing with an approved oxygen compatible leak detection fluid.
General
Servicing is usually required if gas escapes from the hand torch when it is on
the hanger rod; test by hand pressure on the hanger rod.
If the torch and station outlet valves are closed, but the regulator indicates a
slow change in pressure when the torch is off the hook, the quad-ring seal in
the Mizer may be damaged. Damage to this seal will allow gas to escape past
the thrust pin seal. This condition may also be caused by a hose connection;
test with an approved oxygen compatible detection fluid.
Valve Seat Replacement
Send faulty equipment to a CONCOA-designated repair center for repairs.
Use only lubricants compatible with oxygen.
NOTE
IMPORTANT
CAUTION
CAUTION
5