[AnyWireASLINK Terminal]
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending
on the load current. If the load current is small, using a two-wire (non-isolated) terminal
allows for achieving simpli ed wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of
connections, hybridization with a four-wire (isolated) terminal, which supports local
power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving
using an external power supply.
[System Configuration Example]
■Connection with a 2-wire (non-isolated) terminal only
Red: DP
AnyWireASLINK
Black: DN
master
Brown
×
×
Open power lines (brown & white)
Protect these lines so that they won't
*
24V DC
come in contact with other devices.
*
Make sure to use a 24V DC stabilized power supply
for the power supply to be connected.
*
When complying with the UL Standard, make sure
to use a 24V DC stabilized power supply of "NEC
Class 2 Output."
B
B
1: 24V
2: DP
3: 0V
4: DN
Y-Joint Plug/Socket
XS5R-D426-5 (OMRON Corporation)
ASLINKSENSOR
C
Retrore ective type (IP67)
ASLINK
TERMINATOR (IP67)
A Waterproof trunk cable (1.25mm
)
2
Model
Description
Loose wires on one end,
BL2-0C1S-3K
straight M12, 3m
C Waterproof branching unit
Description
Model
BL2109-04-22
4 ports
8 ports
BL2109-08-22
■Relationship between the size and length of
the transmission line and the supply current (Table 1)
Supply current on the transmission line (DP, DN)
Size of
the transmission
Total length:
line (DP, DN)
50m or less
1.25mm
MAX 2A
2
0.75mm
MAX 1.2A
2
0.5mm
MAX 0.8A
2
- Refer to Table 1 so that the size and length of the transmission
CAUTION
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the AnyWireASLINK
master and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the "total line length."
- Connect the terminator BT0 (with polarity) on the transmission line terminal
farthest from the AnyWireASLINK master unit.
A
ASLINKSENSOR
Proximity type
White
(ampli er relay type) (IP67)
ASLINKSENSOR
Proximity type (IP67)
C
General-purpose
sensors cannot be
connected to the
CAUTION
branching unit.
ASLINKSENSOR
Transmissive type (IP67)
General-purpose
sensors cannot be
connected to the
CAUTION
branching unit.
B Waterproof trunk cable (1.25mm
Model
Description
BL2-1S1P-3K
Straight M12 on both ends, 3m
BL2-1S1P-5K
Straight M12 on both ends, 5m
BL2-1S1P-10K
Straight M12 on both ends, 10m
Total length: Over 50m,
Total length: Over 100m,
no longer than 100m
no longer than 200m
MAX 1A
MAX 0.5A
MAX 0.6A
MAX 0.3A
MAX 0.4A
MAX 0.2A
■Example of mixed installation with 2-wire (non-isolated) and
4-wire (isolated) terminals
AnyWireASLINK
master
General-purpose
power supply lter
*
24V DC
Y-Joint Plug/Socket
XS5R-D426-5
(OMRON Corporation)
1: 24V
2: DP
3: 0V
4: DN
ASLINKER
(IP67)
Compact 2-point
I/O terminal
General-purpose
sensor, actuator, etc.
ASLINKSENSOR
Retrore ective type (IP67)
)
2
ASLINK
TERMINATOR (IP67)
A Waterproof trunk cable (1.25mm
Model
BL2-0C1S-3K
C Waterproof branching unit
Model
BL2109-04-22
BL2109-08-22
CAUTION
always use a 4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
-BL21090*22 2/8-
Red: DP
Black: DN
Brown
White
ASLINK
lter
C
B
CAUTION
B
General-purpose
sensor, actuator, etc.
C
General-purpose
sensors cannot be
connected to the
CAUTION
branching unit.
2
)
B Waterproof trunk cable (1.25mm
Description
Model
Loose wires on one end,
BL2-1S1P-3K
straight M12, 3m
BL2-1S1P-5K
BL2-1S1P-10K
Description
4 ports
8 ports
To connect loads (e.g. I/O ports) that are
controlled with a power supply other than the
one used for the AnyWireASLINK system,
A
ASLINKSENSOR
Proximity type
(ampli er relay type) (IP67)
ASLINKSENSOR
Proximity type (IP67)
General-purpose
sensors cannot be
connected to the
branching unit.
The M12 connector is
Smartclick-compatible.
ASLINKSENSOR
Transmissive type (IP67)
2
)
Description
Straight M12 on both ends, 3m
Straight M12 on both ends, 5m
Straight M12 on both ends, 10m