[Various Settings]
Address setting
Teaching
■Common procedure for address writer operation
Be sure to connect to the AnyWireASLINK master unit to use.
Address Writer ARW-04 (Ver. 04-1.01 or later) is required for
operation.
For details about the operation method, refer to the address
writer's Products Guide.
1. Connect the terminal to the AnyWireASLINK master unit.
With the transmission signal (DP/DN) and power supply (24V/0V) being
connected, set parameters with the address writer.
Transmission
signal
ASLINKAMP
White: 0V
* Use a 24V DC stabilized power supply.
2. This setting procedure is required for all terminals.
After opening the protective cover of the terminal subject to setting, direct
the address writer toward the setting port as shown in Fig. 1, and conduct
setting.
(Hold the light emitting/receiving part as close to the setting port as
possible.)
For a terminal that is not subject to setting, keep the protective cover closed.
Light emitting/receiving part
Setting port
LINK
IN
ALM
Fig. 1
Address setting
For address numbers, specify the leading number of the
transmission frames to be allocated to the terminal.
The address numbers of this device are set between 0 and 254.
The factory setting of the terminal is "255,"
CAUTION
which means no setting.
If the address number is set to 255, the
terminal does not perform I/O operations.
Before using the terminal, be sure to set an
address number between 0 and 254.
Example) Address assignment to four ber ampli ers in series
connection
AnyWire address
0
1
2
3
Input
"0" "1" "2" "3"
Addresses to be set
Parameter setting
AnyWireASLINK
Red: DP
master
Black: DN
Green: 24V
*
24V DC
Open the protective
Setting port
cover before setting
Teaching
Teaching operation is intended to register workpiece
presence/absence status in the ASLINKSENSOR.
The setting procedure should be conducted with a workpiece to be
actually used.
To select the "0-100%" mode for the light receiving level indication
setting (equipment parameter 08), be sure to conduct teaching.
[SET ON setting]
With a target workpiece placed in the detecting area, conduct this setting.
Workpiece
[SET OFF setting]
With no target workpiece placed in the detecting area, conduct this setting.
[Automatic setting for teaching]
If you conduct teaching when "AD value indication" is selected for
the light receiving level indication setting (equipment parameter 08),
"threshold," "hysteresis," "alarm Hi" and "alarm Lo" values will be
automatically calculated and set at the following ratio, based on
the difference in AD value between SET ON status (workpiece is
present) and SET OFF status (no workpiece).
*
When the "0-100%" mode is selected for light receiving level
indication setting (equipment parameter 08), the automatic
setting function for teaching is disabled.
Example)
① SET ON
② SET OFF
With the difference in AD value between SET ON status and SET
255
OFF status de ned as the reference (100%), the following
parameters will be automatically set.
Threshold (Equipment parameter 01): 490 (50%)
Hysteresis (Equipment parameter 02): 49 (5%)
Alarm Hi (Equipment parameter 03): 784 (80%)
Alarm Lo (Equipment parameter 04): 196 (20%)
-L*F1011 7/11-
Red: DP
Black: DN
Green: 24V
White: 0V
Red: DP
Black: DN
Green: 24V
White: 0V
Threshold
50%
Hysteresis
5%
Alarm Hi
80%
20%
Alarm Lo
AD value for workpiece
present status is "0."
AD value for workpiece
absent status is "980."
AnyWireASLINK
master
AnyWireASLINK
master