3P Technik DTC200 설치 및 운영 매뉴얼 - 페이지 14

{카테고리_이름} 3P Technik DTC200에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. 3P Technik DTC200 16 페이지.

3P Technik DTC200 설치 및 운영 매뉴얼
Overflow Alarm
1 or more outputs
does not switch off

Fuse Listing

F1 – 500mA 20mm quickblow
F2 – 1A 20mm glass passivated
F3 – 10A 20mm glass passivated
F4 – 10A 20mm glass passivated
F5 – 10A 20mm glass passivated
F6 – 10A 20mm glass passivated
Inputs (left to right) – Con1
1 – Low Alarm (installed below low level sensor)
2 – Low (tank empty)
3 – High (tank full)
4 – Overflow (installed above high level sensor)
5 – unused

Pressure Sensor Inputs (left to right)

Con3 (left) – unused
Con4 (right) – unused
DTC200 V1.20
Sensor activated
Sensor not present
Sensor disconnected
Sensor activated
Sensor not present
Sensor failure
Relay welded open (LED
above relay not lit but
output still live)
Page 14
Check drain valves and tank
integrity. Check output to drain
pump.
Disable alarm function from
menu or install sensor
Check wiring
Check output to filling and
dosing pumps
Disable alarm function from
menu or install sensor
View sensor status from the
diagnostic menu or test sensors
with continuity meter and
correct.
Replace PCB.
22/01/20