■ General technical data

AC line supply (R,S,T):
Supply voltage 380-440 V units
Supply frequency
Max. imbalance of supply voltage:
HLP-V 4015-4550V
True Power factor ()
Displacement Power Factor (cos .)
No. of switches on supply input R, S, T
Max. shortcircuit rating
HLP-V output data (U, V, W):
Output voltage
Output frequency HLP-V 4015-4050, 380-440 V
Output frequency HLP-V 4060-4215, 380-440 V
Output frequency HLP-V 4350-4550, 380-440 V
Rated motor voltage, 380-440 V units
Rated motor frequency
Switching on output
Ramp times
Torque characteristics:
Starting torque, HLP-V 4015-4550V
Starting torque
Acceleration torque
Overload torque, HLP-V 4015-4550
Arresting torque at 0 rpm (closed loop)
The torque characteristics given are for the adjustable frequency drive at the high overload torque level
(160%). At the normal overload torque (110%), the values are lower.
Control card, digital inputs:
Number of programmable digital inputs
Terminal no.
Voltage level
Voltage level, logical '0'
Voltage level, logical '1'
Maximum voltage on input
Input resistance, Ri
Scanning time per input 3 msec.
Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition,
the digital inputs can be isolated from the other terminals on the control card by connecting an external 24 V
DC supply:
6
HLP-V Series
3 x 380/400/415/440 V ±10%
48-62 Hz +/- 1 %
±2.0% of rated supply voltage
0.90 nominal at rated load
near unity (>0.98)
approx. 1 time/2 min.
100,000 A
0-100% of supply voltage
0-132 Hz, 0-1000 Hz
0-132 Hz, 0-450 Hz
0-132 Hz, 0-300 Hz
380/400/415/440 V
0.05-3600 sec.
160% for 1 min.
180% for 0.5 sec.
16, 17, 18, 19, 27, 29, 32, 33
0-24 V DC (PNP positive logics)
>10 V DC
50/60 Hz
Unlimited
100%
160%
100%
8
< 5 V DC
28 V DC
2 k