Danfoss VLT AutomationDrive FC 361 설치 매뉴얼 - 페이지 2

{카테고리_이름} Danfoss VLT AutomationDrive FC 361에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss VLT AutomationDrive FC 361 8 페이지.

Installation Guide | VLT® PROFINET MCA 120
2 Safety

2.1 Safety Precautions

DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death
or serious injury.
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
-
DC-link connections to other drives.
Wait for the capacitors to discharge fully. The minimum waiting time is specified in table Discharge time and is also visible
-
on the nameplate on top of the drive.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
-
are fully discharged.
Table 1: Discharge Time
Voltage [V]
Power range [kW (hp)]
380–480
90–315 kW (125–450 hp)
2 | Danfoss A/S © 2019.03
W A R N I N G
Minimum waiting time (minutes)
20
AN274237376992en-000101 / 130R0856
Safety