Installation Instructions
LOP Connection and Set-up
1.1.1 Items Supplied
Local operating panel (LOP), 175N0128 IP 65, see
Illustration 1.1
Fixture for LOP, 175N2717 (included in 175N0128),
see Illustration 1.2
LOP cable
Illustration 1.1 Local Operation Panel (LOP) 175N0128 IP 65
Illustration 1.2 Fixture for LOP 175N2717 (included in 175N0128)
1.1.2 Safety Instructions
Refer to VLT
Instructions for detailed information about safety precautions
for installation.
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. Failure to wait the specified time after power
has been removed before performing service or repair work,
could result in death or serious injury.
1) Power ratings relate to NO, see VLT
Operating Instructions.
Danfoss A/S © Rev. 2013-12-02 All rights reserved.
®
DriveMotor FCP 106 and FCM 106 Operating
WARNING
1.
Stop motor.
2.
Disconnect AC mains, permanent magnet type
motors, and remote DC-link power supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.
3.
Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in Table 1.1.
Voltage
Power Range
[V]
[kW]
3x400
0.55–7.5
High voltage can be present even when the warning LED indicator
lights are off.
Table 1.1 Discharge Time
Minimum waiting
1)
time
(min)
4
®
DriveMotor FCP 106 and FCM 106
MI03L102