Danfoss KP 63 지침 - 페이지 3

{카테고리_이름} Danfoss KP 63에 대한 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss KP 63 4 페이지. Vapour charge, adsorption charge (cross ambient)
Danfoss KP 63에 대해서도 마찬가지입니다: 설치 매뉴얼 (2 페이지), 설치 매뉴얼 (4 페이지)

Danfoss KP 63 지침
Adjustment spindles location
Note!
Remove lockplate before thermostat
adjustment. Replace lockplate after
adjustment (if desired).
RANGE
See printed instruction on top of control
increase temp. (warmer): turn CW
decrease temp. (colder): turn CCW
(use adjustment knob)
Determination of diff erential
For KP w/ vapor charge and auto. reset (KP 61, KP 62, KP 63, KP 68, KP 69): Use graphs to determine correct diff erential
Example:
HSP = +45°F (+5.6°C)
=>
LSP = +32°F (0°C
© Danfoss A/S
DIFF (from graph):
13°F (7.2°C) (value which has to be
set on diff . scale).
RI.5D.A2.22 → DKRCC.PI.C0A.A1.22-520H2749
DIFFERENTIAL
See printed instruction on top of control
Increase: turn CW
decrease: turn CCW
(use adjustment knob or screwdriver)
For KP w/ adsorption charge (KP 71, KP 73, KP 75, KP 77, KP 79, KP 81):
The diff erential will be HSP less LSP
Example:
HSP – LSP = DIFF.
45°F – 35°F = 10°F
(7°C)
(5°C)
Note:
(Load Option A)
(Load Option B)
CUT-IN
= HSP or
CUT-IN
CUT-OUT = LSP
CUT-OUT = HSP
See "Wiring"
(2°C)
= LSP
3