Installation Instructions
1.4.2 Removing the Inrush Card in D2h/D4h/D7h/D8h Drives
To remove the inrush card, use the following steps. Refer to Illustration 1.5.
1.
Unplug the cable from the inrush card connector MK1802.
2.
Remove 2 thread-forming screws (T20).
3.
Remove 5 screws (T20) from the inrush card.
4.
Remove the inrush card from the drive, and discard it.
1
MK1802
2
MK1800
3
Screw (T20)
4
MK102
5
MK100
6
MK501
Illustration 1.5 Inrush Card and Gatedrive Card
MI39A102
Inrush Card Kit for D1h–D8h Drives
®
VLT
FC Series FC 102, FC 103, FC 202, FC 302
7
Inrush card
8
Screw (T20)
9
MK101
10
Gatedrive card
11
MK701
12
MK601