Danfoss EKE 1P 사용자 설명서 - 페이지 9

{카테고리_이름} Danfoss EKE 1P에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss EKE 1P 16 페이지. Stepper valve extension module, adap-kool refrigeration control system

Danfoss EKE 1P 사용자 설명서
User Guide | Stepper Valve Extension Module, Type EKE 1P
Valve config
Any changes made to parameters in this group will only take effect after a restart of the
controller, e.g. by a power cycle or by toggling the main switch.
Valve configuration
Application 1: Set from AK-PC except if the valve type is set to User Defined in AK-PC,
then it is according to below list (see Application mode 2).
Application 2:
0 = no valve, 1 = UserDef,
2 = ETS 12C, 3 = ETS 24C, 4 = ETS 25C, 5 = ETS 50C, 6 = ETS 100C,
7 = ETS 6, 8 = ETS 12.5, 9 = ETS 25, 10 = ETS 50, 11 = ETS 100,
12 = ETS 250, 13 = ETS 400,
14 = KVS 2C, 15 = KVS 3C, 16 = KVS 5C,
17 = KVS 15, 18 = KVS 42,
19 = CCMT 0, 20 = CCMT 1,
21 = CCMT 2, 22 = CCMT 4, 23 = CCMT 8,
24 = CCMT 16, 25 = CCMT 24,
26 = CCMT 30, 27 = CCMT 42,
28 = CCM 10, 29 = CCM 20, 30 = CCM 30, 31 = CCM 40,
32 = CTR 20
33 = CCMT 3L, 34 = CCMT 5L, 35 = CCMT 8L
Valve fallback OD
During fail-safe mode in application 1 (e.g. CANBUS signal lost), the valve will apply this
opening degree.
Valve motor type
Define a type of motor used in the stepper valve (Unipolar/Bipolar).
Valve drive current
The current applied to each phase of the stepper motor during actual valve movement.
Entered as a peak value.
Valve step
Read-out of the valve opening degree in number of steps.
positioning
Valve total steps
The number of steps that correspond to changing the valve position from 0 – 100% OD.
Valve speed
The desired valve drive rate in steps per second.
Please note that a higher valve speed will produce a lower torque. If the valve is used in
systems having high differential pressure, it is better to operate the valve with a lower
step rate.
Valve start speed
This is used to limit the starting speed of the valve in order to provide higher motor
torque at start-up to prevent the valve from potential step loss.
Valve emengency
During power failure conditions, the valve can be driven at higher speed when required
speed
to close faster. This function requires a back-up battery connected to the EKE.
Valve acceleration
These features are used with valves running at higher speed i.e 300 pps and above.
current
Typically, at start-up high torque is required to operate the valve. The high torque at
start-up can be maintained by using acceleration current as required.
Valve acceleration
time
Valve holding current The percent of the programmed Max Phase Current that should be applied to each
phase of the stepper output when the valve is stationary. If required, this current
ensures that the valve maintains its last programmed position.
Valve step mode
Stepper motor can be driven with various step excitation methods, depending on valve
requirements and operating conditions.
The valves can be driven in full step 1/1, half step 1/2, or in microsteps (1/4, 1/8, 1/16).
Valve duty cycle
The required valve duty cycle can be set between 5-100% using this parameter.
Valve OD during stop The valve will apply this opening degree if the control is stopped (main switch off ).
Start backlash
The parameter defines the operation of the start backlash function. The valve will
normally open from this point onwards.
Compensation
This setting is used to correct for mechanical hysteresis of the valve's designs including a
backlash
reduction gear. To ensure that the gear backlash is at a minimum, the motor will drive a
number of extra steps every time the direction of the motor is changed.
Overdrive
When the overdrive is enabled and the block timer has expired, next time the valve
closes to 0% OD, it will close with some extra steps according to this setting.
Overdrive enable OD After being closed, the valve opening degree must exceed this value before the
overdrive function is enabled again.
Overdrive block time After an overdrive has occurred, the overdrive function may not occur again within this
time.
Valve excitation time
The time that the drive current is applied after the motor has stopped before going to
after stop
holding current. This will make sure that the valve has achieved the final position before
going to holding current.
© Danfoss | DCS (vt) | 2020.03
Fac: no valve
0 – 100%
Fac: 0%
Unipolar / Bipolar
Fac: Unipolar
10 – 1000 mA
Fac: 10 mA
1 – 8000 steps
Fac: 1 step
10 – 400 pps
Fac: 10 pps
1 – 100%
Fac: 20%
50 – 200%
Fac: 100%
100 – 150%
Fac: 100%
10 – 150 ms
Fac: 10 ms
0 – 300%
Fac: 0
Full, Half, 1/4, 1/8, 1/16
Fac: 1/8
5 – 100%
Fac: 100%
0 – 100%
Fac: 0%
0 – 50%
Fac: 0.0%
0-10%
Fac: 0.0%
0 – 20%
Fac: 5.0%
0 – 100%
Fac: 0%
0 – 1440 min.
Fac: 10 min.
0 – 1000 ms
Fac: 10 ms
BC320219567793en-000201 | 9