Danfoss EVR 15 설치 매뉴얼 - 페이지 2

{카테고리_이름} Danfoss EVR 15에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss EVR 15 2 페이지. Solenoid valve
Danfoss EVR 15에 대해서도 마찬가지입니다: 설치 매뉴얼 (2 페이지)

Danfoss EVR 15 설치 매뉴얼
Disassembly and assembly of EVR version 2
Mounting / dismounting of top part
EVR 2 – EVR 8
Type
[Nm]
EVR 2, EVR 3,
3.0
EVR 4, EVR 6, EVR 8
Mounting of support washer
EVR 2 – EVR 3 (NC)
Manual operation for pressure testing and service related operation:
Only use the manual stem operation of the EVR NC valve during initial pressure testing of the refrigeration system or during service related
manual operation. Remove the protective cap and rotate the manual stem clockwise approx. 6 cycles from fully closed to fully open
position. After the manual operation is completed, ensure to rotate the manual stem counter-clockwise back to fully closed position and
re-mount the protective cap before connecting the valve to automatic operation. MOPD for the manual operation function is 5 bar.
Alternatively, all EVR NC and NO valves can be manually operated by removing the coil and force the valve open or closed by using a
solenoid valve tester (permanent magnet).
© Danfoss | DCS (rm) | 2020.11
4
1
2
3
Note!
Always use
cross-tightening
[kpm]
[ft-lbs]
Torx size
0.3
2.2
EVR 4 – EVR 8 (NC)
EVR 10 – EVR 22 (NC)
Mounting / dismounting of top part
EVR 10 – EVR 22
Type
EVR 10, EVR 15, EVR 18
T15
EVR 20, EVR 22
Special for EVR 4 – EVR 8:
Dismounting gasket and supporting ring
B
B
A
A
Caution!
For EVR 2 – EVR 3, and EVR 10 – EVR 22, a screwdriver might be needed
for removal of the gasket. Be careful not to scratch the gasket surface.
EVR 4 – EVR 8 (NO)
4
2
Note!
Always use
cross-tightening
[Nm]
[kpm]
[ft-lbs]
10
1
7.4
30
3
22.1
EVR 10 – EVR 20 (NO)
AN238486497127en-000704 | 2
1
3
Torx size
T30
T45