15. Flame sensor: ionisation electrode
Single electrode operation, ionisation
MPA connector
15: Ignition
3: N
4: PE
5: ION*
7: FLW power
16: FLW2 NO
*When using a DUNGS DEZ 1xx SEO ignition transformer for single electrode operation,
the green / yellow line must be connected to terminal 5.
Two electrode operation, ionisation
MPA connector
15: Ignition
3: N
4: PE
5: ION
7: FLW power
16: FLW2 NO
11 ... 16
16. Approved flame detectors
Manufac-
turer
Flame
DUNGS
DUNGS
DUNGS
BST
Solutions
BST
Solutions
Flame
Designation
Type
Output
signal
Ionisation
Ionisation
Ionisation
–
electrode
UV tube
Ionisation
UV41 (HE)
UV tube
Switching
UV42
output
230 VAC
Ionisation
Switching
FLW 41I
output
230 VAC
FLW 20
(KLC 1000)
KLC 10/230
KLC 1000/230
FLW 20 UV
UV tube
Ionisation
KLC 10/230 RA
KLC 1000/230
RA
FLW 10 IR V2.1
KLC 2002
Flicker
FLW 10 IR
detection
with
KLC 2002
Ionisation
frequency
FLW 10 IR V2.1
monitoring
KLC 20/230
When using flame detectors, the reation times must be observed and adjusted by correctly setting the
corresponding parameters.
Safety
Total reacti-
Inter-
Continuous
time
on time after
mit-
operation
Flame
flame lift-off
tent
detector
0 s
P41
Yes
No
0,125 s
P41 + 0,125 s
Yes
No
(= 2/16 s)
0,125 s
P44 + 0,125 s
Yes
No
(= 2/16 s)
0,19 s
P44 + 0,19 s
Yes
No
(= 3/16 s)
0,5 s
P41 + 0,5 s
Yes
No
0,5 s
P41 + 0,5 s
Yes
No