Danfoss VLT HVAC Drive FC 102에 대해서도 마찬가지입니다: 운영 매뉴얼 (16 페이지), 설치 매뉴얼 (20 페이지), 설치 지침 매뉴얼 (6 페이지), 설치 지침 매뉴얼 (12 페이지), 설치 매뉴얼 (18 페이지), 설치 지침 매뉴얼 (11 페이지), 설치 지침 매뉴얼 (8 페이지), 설치 매뉴얼 (6 페이지), 사용 설명서 (16 페이지), 설치 지침 매뉴얼 (6 페이지), 설치 매뉴얼 (16 페이지), 설치 매뉴얼 (8 페이지), 사용 설명서 (16 페이지), 설치 지침 매뉴얼 (6 페이지), 설치 매뉴얼 (6 페이지)

Danfoss VLT HVAC Drive FC 102 설치 지침 매뉴얼

Installation Instructions

500 A Current Sensor Kit for
E1/E2 Enclosure Sizes
®
VLT
FC 102, FC 103, FC 202, FC 302
1.1.1 Description
The 500 A current sensor kit is designed for E1 and E2
enclosure sizes in the power ranges shown in Table 1.1. To
identify the power rating, see Illustration 1.1.
Product group and series
®
VLT
HVAC Drive FC 102,
®
VLT
Refrigeration Drive FC 103,
®
VLT
AQUA Drive FC 202
®
VLT
AutomationDrive FC 302
Table 1.1 Applicable Power Range for 500 A Current Sensor Kit
The 500 A current sensor kit contains all components required
to upgrade the current sensors in E1 and E2 enclosure sizes.
1.1.2 Identifying the Power Rating
To find the frequency converter power rating, use the
following steps.
1.
Obtain the following information from the
nameplate, which is on the frequency converter.
Refer to Illustration 1.1.
1a
Product group and product series
(characters 1–6)
1b
Power rating (characters 7–10)
1c
Voltage rating (phases and mains)
(characters 11–12)
Determine if the power rating is in Table 1.1.
2.
Voltage rating
Power rating
(T4/T5) 380–
315 kW
480 V
(450 hp)
(T7) 525–690 V 450–560 kW
(450–600 hp)
(T5) 380–500 V 250 kW
(450 hp)
(T7) 525–690 V 355–500 kW
(450–600 hp)
Danfoss A/S © 10/2016 All rights reserved.
1
Product group and product series
2
Power rating
3
Voltage rating (phases and mains)
Illustration 1.1 Nameplate Information for a Frequency Converter
1.2 Kit Part Number
Part number
Kit description
176F3746
500 A Current sensor kit for E1/E2 enclosure sizes
Table 1.2 Part Number for the Current Sensor Kit

1.2.1 Items Supplied

The 500 A Current Sensor Kit for E1 and E2 enclosure sizes
contains the following parts.
Quantity Item description
3
500 A current sensor and busbar
3
Current sensor bracket
1
Wire harness and cable ties
12
Hex nuts (M4) and washers
Table 1.3 500 A Current Sensor Kit Parts List
MI92Q102