Danfoss VLT MCD 200 설치 지침 매뉴얼 - 페이지 7

{카테고리_이름} Danfoss VLT MCD 200에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss VLT MCD 200 17 페이지. Usb module
Danfoss VLT MCD 200에 대해서도 마찬가지입니다: 설치 지침 매뉴얼 (6 페이지), 설치 지침 (5 페이지)

Danfoss VLT MCD 200 설치 지침 매뉴얼
MCD Modbus Module Instructions

8. Modbus Functions

The Modbus Module supports the following Modbus functions:
03 Read multiple registers
06 Write single register
Modbus broadcast functions are not supported.
MCD 200 soft starters (including Remote Operator):
Read multiple registers 40003 to 40008
Write single register 40002
MCD 500 soft starters:
Read multiple registers starting from 40003 up to a maximum of 125 register blocks
Write single register 40002 or 40009 to 40599

8.1. Master Configuration

For standard Modbus 11-bit transmission, the Master must be configured for 2 stop bits with No
Parity and 1 stop bit for odd or even parity.
For 10-bit transmission, the Master must be configured for 1 stop bit.
In all cases, the Master baud rate and slave address must match those set on the Modbus Module DIP
switches.
Command: Start
Message
In
Out
Starter status: Running
Message
In
Out
Trip code: Motor overload
Message
In
Out
Download parameter from starter
MCD 500: Read Parameter 1, Motor FLC (Parameter 1-1), 100 A
Message
In
Out
N.B.!:
A multiple read across register boundary 40008/40009 will result in a Modbus Error code
05 at the Master.
Modbus Module version 3 and earlier (serial number xxxxxx-3) can read a maximum of
119 register blocks.
Starter
Function Code
Address
20
20
Starter
Function Code
Address
20
20
Starter
Function Code
Address
20
20
Starter
Function
Address
Code
20
20
MG.17.F5.02 - VLT® is a registered Danfoss trademark
Register
Address
06
40002
06
40002
Register
Address
03
40003
03
2 (bytes)
Register
Address
03
40004
03
2 (bytes)
Register
Address
03
40009
03
2 (bytes)
Modbus Functions
Data
CRC
1
CRC1, CRC2
1
CRC1, CRC2
Data
CRC
1
CRC1, CRC2
3
CRC1, CRC2
Data
CRC
1
CRC1, CRC2
2
CRC1, CRC2
Data
CRC
1
CRC1, CRC2
100
CRC1, CRC2
7