Danfoss iSave 21 서비스 매뉴얼 - 페이지 7

{카테고리_이름} Danfoss iSave 21에 대한 서비스 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss iSave 21 18 페이지. Energy recovery device disassembling and assembling

Danfoss iSave 21 서비스 매뉴얼
Service guide
4.
Assembling the
pressure exchanger
Disassembling and assembling iSave 21
IMPORTANT:
It is essential that the iSave is serviced in
conditions of absolute cleanliness.
All Parts must be absolute clean before
mounting.
Lubrication
- To prevent seizing-up, lubricate threads on
screws.
- O-rings inside iSave may be lubricated only
with clean filtered water.
1.
Mount the new back-up rings on the
valve plate first and then the new O-rings.
3.
Lubricate all the O-rings and back up
rings with clean filtered water and gently
by help of the 3 compression tools in
every fourth hole mount both valve plate
on the cylinder barrel.
180R9219 | 521B1171 | DKCFN.PI.003.K4.02 | 03.2016
WARNING:
Do not use silicone when assembling the
iSave. Do not reuse dismantled O-rings: they
might be damaged. Always use new O-rings.
- O-rings for port flange, mounting flange may
be lubricated with a small amount of grease.
- It is important to lubricate ALL parts to be
assembled with clean filtered water (Especially
all PEEK parts).
2.
Lubricate all the bores in the cylinder
barrel with clean filtered water.
4.
Adjust the distance between the cylinder
barrel and valve plate at the short
shaft end. Distance 4-6 mm.
7