Danfoss 176F4041 설치 매뉴얼 - 페이지 7

{카테고리_이름} Danfoss 176F4041에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss 176F4041 18 페이지. In-bottom/out-back cooling kit for fa09-fa10, frequency converters

In-bottom/Out-back Cooling Kit for FA09-FA10
Installation Guide
74 (2.9)
8x Ø 6 (0.2)
2x Ø 8 (0.3)
Drive Mounting Holes
Illustration 4: FA10 Mounting Plate Template for In-bottom/Out-back Cooling
2.4 Preparing the Backplate
To create a vent opening in the cabinet backplate to match the opening in the mounting plate, use the following steps. Use the
dimensions in
Illustration 5
for FA09 frequency converters, and
Procedure
1.
Cut out the vent opening in the cabinet backplate using the dimensions in the template.
The vent opening must match the mounting plate opening.
2.
Drill screw holes (6 mm) around the vent opening using the dimensions in the template.
The FA09 requires 6 holes around the vent opening, and the FA10 requires 8 holes around the opening. The holes must
align with the holes in the outer flanges of the back vent.
Danfoss A/S © 2022.03
321 (12.6)
280 (11.0)
2x Ø 8 (0.3)
Drive Mounting Holes
10 (0.4)
271 (10.7)
Illustration 6
for FA10 frequency converters.
110 (4.3)
130 (5.1)
1051 (41.4)
AN371942757356en-000101 / 136R0252 | 7