In-bottom/Out-back Cooling Kit for FA11-FA12
Installation Guide
2.3 Creating Vent Opening in the Mounting Plate
To create mounting holes and a back vent opening in the mounting plate, use the following steps. Use the dimensions in
3
for FA11 frequency converters in 600 mm (24 in) cabinets, and
cabinets. Use the dimensions in
Procedure
1.
Drill 6 mounting holes in the back of the frequency converter using the dimensions in the template.
2.
Insert 6 M10 pem self-clinching nuts (not supplied) in the mounting holes.
3.
Cut out the vent opening in the mounting plate using the dimensions in the template.
The opening must match the frequency converter vent opening.
4.
Drill 6 screw holes around the vent opening using the dimensions in the template.
The holes must match the holes in the inner flange of the back duct.
6X S-M10-2Z1
3 (0.1)
Illustration 3: Vent Dimensions for FA11 Mounting Plate in 600 mm (24 in) Cabinet
Danfoss A/S © 2022.12
Illustration 5
for FA12 frequency converters in 800 mm (32 in) cabinets.
7 (0.3)
Illustration 4
for FA11 frequency converters in 800 mm (32 in)
499 (19.7)
Installation
23 (0.9)
0.0
100 (3.9)
2X 137 (5.3)
158 (6.2)
169 (6.7)
314 (12.3)
326 (12.8)
2X 347 (13.7)
1645 (64.7)
AN361429392581en-000201 / 136R0253 | 5
Illustration