In-bottom/Out-back Cooling Kit for FA11-FA12
Installation Guide
2.11 Installing the Backplate and Back Duct
To attach the cabinet backplate and the back duct, use the following steps.
Procedure
1.
Position the backplate on the back rails of the cabinet behind the mounting plate.
2.
Secure the backplate to the rails using the existing fasteners.
3.
Slide 8 M5 clip-on nuts over the screw holes around the duct opening in the backplate.
4.
Remove the paper backing from both 8-hole gaskets, exposing the adhesive.
5.
Adhere 1 gasket to the back and 1 gasket to the front of the back duct outer flange.
6.
Position the back duct in the hole created for it in the mounting plate and backplate.
7.
Fasten the inner flange of the back duct with 6 M6x12 screws (T30).
Torque to 3.9 Nm (35 in-lb).
8.
Fasten the outer flange of the duct with 8 M5x18 screws (T25).
Torque fasteners to 2.3 Nm (20 in-lb).
Danfoss A/S © 2022.12
Installation