Danfoss VLT AQUA Drive FC 202 설치 매뉴얼 - 페이지 12

{카테고리_이름} Danfoss VLT AQUA Drive FC 202에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss VLT AQUA Drive FC 202 18 페이지. Igbt module replacement for d1h–d8h drives
Danfoss VLT AQUA Drive FC 202에 대해서도 마찬가지입니다: 운영 매뉴얼 (16 페이지), 설치 매뉴얼 (20 페이지), 설치 지침 매뉴얼 (6 페이지), 설치 지침 매뉴얼 (8 페이지), 설치 지침 매뉴얼 (10 페이지), 설치 매뉴얼 (6 페이지), 사용 설명서 (16 페이지), 설치 지침 매뉴얼 (6 페이지), 설치 매뉴얼 (8 페이지), 설치 지침 매뉴얼 (6 페이지), 설치 매뉴얼 (8 페이지), 설치 매뉴얼 (6 페이지)

Danfoss VLT AQUA Drive FC 202 설치 매뉴얼
Installation

3.8 Electrical Installation

3.8.1 Cabling Requirements
Choose suitable media for Ethernet data
transmission. CAT5e and CAT6 cables are
3
3
recommended for industrial applications. Both
3.8.2 Cable Specifications
PROFINET cables used are based electrically on category 5 balanced LAN cables according to ISO/IEC 11801 Edition 2.0, Class
D.
Type C cables can be used in special applications (for example, the use of trailing cables and frequently moved machine
parts), even though their design and mechanical parameters can deviate from the specifications of type A and type B
cables. Still, most of the electrical parameters (for example, impedance levels) are retained.
Highly flexible copper cables generally have the finest stranded conductors and a highly resistant polyurethane outer
sheath. Various outer sheath materials are permitted to meet the various demands regarding resistance of industrial
environments and exterior/underground laying (natural and synthetic oil, grease, coolants/lubricants, chemicals, high and
low temperatures, UV radiation, and so on).
Cable type
Design
Cable installation type
Cable marking
Core cross-section
Outer diameter
Core diameter
Colour (outer sheath)
Core identification (colours)
star quad 2 pair
Number of cores
Cable design
Shielding design type
Plug type
Table 3.3 Cable Specifications for Application Types A, B and C
Relevant standard
Delay skew
Transfer impedance
Table 3.4 Transmission Performance Requirements
10
Installation Guide
Application type A
Application type B
Data Cable
Data Cable
Stationary, no movement
Flexible, occasional movement
after installation
or vibration
PROFINET type A
PROFINET type B
AWG 22/1
AWG 22/7
5.5–8.0 mm
1.5 ± 0.1 mm
Green RAL6018
White, yellow, blue, orange
Pair 1: white (RXD+), blue (RXD-) Pair 2: yellow (TXD+), orange (TXT-)
4
2 pairs or 1 star quad
Aluminium foil + Cu braiding
RJ 45 (IP20 or IP65/67)/M12
ISO/IEC 11801 Edition 2.0, IEC 61156
(minimum Category 5)
≤20 ns/100 m
≤50 m Ω/m at 10 MHz
Danfoss A/S © Rev. 07/2014 All rights reserved.
types are available as unshielded twisted pair and
shielded twisted pair.
Screened cables are recommended for use in
industrial environments and with frequency
converters.
A maximum cable length of 100 m is allowed
between the switches.
Application type C
Data Cable
Special applications (for example, highly flexible,
permanent movement, vibration, or torsion)
PROFINET type C
AWG 22/..
Application dependent
Application dependent
Application dependent
Application
MG90U402