Installing unit with 3105007.XXX or 3105935.XXX
Return Air Cover, continued from page 13, column A.
3. Place divider plate up to bottom of air conditioner
base pan firmly. The foam tape on the divider plate
must seal to bottom of base pan. See FIG. 14A.
Note: The adhesive on the insulation is extremely
sticky. Be sure the part is located where desired
before pressing into place.
4. With slight pressure then push the divider plate
CAUTION
CAUTION
Improper installation and sealing of divider
plate will cause the compressor to quick
cycle on the cold control. This may result in
fuse or circuit breaker opening and/or lack of
cooling.
Push Divider Firmly To Base
Pan And Divider
against the double sided tape on the ceiling tem-
plate.
5. Locate the 1/8" x 7" x 18" self -adhesive insulation
supplied with the return air kit. Remove the backing
paper from the insulation and carefully stick onto
the ceiling template divider panel. See FIG. 15A.
a. Excess width is intended to seal the divider plate
to the sides of the 14-1/4" x 14-1/4" (±1/8")
opening. This is to help prevent cold air discharge
from circulating into the air conditioner return
air opening.
b. If the insulation is to high, stick excess height
of insulation to the air conditioner base pan. Do
not cover up unit rating plate.
Place Insulation In Position
(Do Not Cover Unit Rating Plate)
FIG. 15A
FIG. 14A
14
INSTALLATION INSTRUCTIONS DUCTED BI-METAL