Troubleshooting

The Problem
The device does not start up
The FAULT LED lights up
The OVERLOAD SENSOR LED lights up
The OVERLOAD BATTERY LED lights up
The control unit is repeatedly issuing an alarm
The control unit is issuing an alarm and does not
shut off the devices connected to it
A 12V DC solenoid valve, which does not work well, is
connected to the BX150
If you are experiencing difficulties, having made the checks listed above call Duomo on 01905 797989 for
technical assistance.
In case of alarm
Extinguish any naked flames.
Do not switch lights or electrical devices on or off.
Open all windows and doors to increase ventilation.
If the 'ALARM' LED is off the levels of gas have dropped. A responsible, qualified person is now safe to find the cause of
the alarm.
If the alarm sound remains constant, and the cause is not evident or possible to eliminate turn off the emergency
isolation valves to the area and contact your gas provider emergency line. They will advice accordingly.
w: www.duomo.co.uk
-
The Solution
Check that the 230V mains power is correctly
connected. If powered by the battery, check that the
12V DC power is correctly connected.
Check that the connecting cables from the BX150 to
the sensors are intact, that the sensors are properly
powered and that the signal cable is correctly
connected.
Check that;
- the power polarity has not been inverted
- that no short-circuit is present
- that the probes were not damaged during
installation, that no excessive current absorption
is present
Check that the connection cables are not
shortcircuited, that the polarity has not been
inverted and that the battery is not damaged.
Check that there are no gas leaks. If the alarm signal
and the FAULT indicator light turn on together, check
the sensor.
Check that the wiring is correct and that the DIP
switch has been set properly. All relays must be free
from electrical power. Check the drawing of the
connections.
Direct connection of 12V DC solenoid valves or sirens
to the BX150 is not permitted. An external power
unit must always be used. The BX150 gives a
maximum current of 50mA.
-