Duomo BX308 XP 빠른 시작 매뉴얼 - 페이지 9

{카테고리_이름} Duomo BX308 XP에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Duomo BX308 XP 17 페이지. 8 sensor gas detection controller

BX308 XP Gas Detection Controller
Pre-alarm Settings
Alarm 20%LEL-20
Prealarm 09%LEL
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
◄► - Select Sensor
ENTER - Choose Pre alarm settings for selected sensor
Return to Memory Settings
Continue to Alarm
Alarm Settings
Alarm 20%LEL-20
1 2 3 4 5 6 7 8
◄► - Select Sensor
ENTER - Choose Alarm settings for selected sensor
Return to Pre Alarm
Continue to OP Range
OP Range Settings
Op Range 20%LIE
1 2 3 4 5 6 7 8
◄► - Select Sensor
ENTER - Choose Alarm settings for selected sensor
Note: Oxygen sensors operating range is factory set to 20%
Given the importance of this operation a confimation screen
will appear. Select between YES/NO with ENTER
The operating range will change from 20% to 100% of LEL.
Remember to change Sensor too.
Return to Alarm
Select to return to MAIN MENU
Exit
ENTER - Select to return to MAIN SCREEN
t: 01905 797989
e: [email protected] | w: www.duomo.co.uk
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault
9

General Settings

Relay: Continuous
Positive Safety: ON
Siren: ON
Buzzer: ON
▼▲ - Choose menu option
ENTER - Choose settings
Relay: CONTINUOUS/PULSED
Continuous: Relay remains closed for entire duration
of alarm condition (If memory is selected, the relay
will remain switched until RESET button is pressed)
Pulsed: The relay reamins closed for 20 seconds, after
which it is de-energised
Positive Safety: ON/OFF
Depending on the type of system, there may be a need to
select Positive Safety. In this mode the operation of the two
manual alarm relays is reversed.
Selection
Use the ▼▲ keys to select the Sic message. Positive Safety.
Each time the "ENTER" button is pressed, the ON / OFF
message will change.
In the "ON" position, the Positive Safety function is activated.
In the "OFF" position, the Positive Safety function is
deactivated.
Once chosen, move with the ▼▲ buttons on the next
selection.
Siren: ON/OFF
Select the word Siren with the ▼▲ keys
Each time the "ENTER" button is pressed, the ON / OFF
message will change.
In the "ON" position the Siren is enabled; The LED on the
panel goes out.
In the "OFF" position the Siren is silenced; The LED on the
panel lights up.
Buzzer: ON/OFF
Select the word Buzzer with the ▼▲ keys
Each time the "ENTER" button is pressed, the ON / OFF
message will change.
In the "OFF" position the Buzzer is silenced.
In the "ON" position the Buzzer is enabled.
Continue to Advanced Settings
Power
Pre Alarm
Battery
Main Alarm
OL Probes
Exit Alarm
OL Battery
Siren Status
Fault